For some NGC installations, it may be necessary to install an optional sample
system conditioning module to compensate for non-ideal natural gas samples.
These optional modules are pre-engineered to provide various levels of protection
and bypass flows (see Figure 1—22). All of the sample conditioning modules
include a level of particulate protection and come in two flow sizes: 50CC
(2102023-xxx) and 450CC (2102024-xxx) per minute (see Table 1–10).
For installations where the gas is ideal and the sample probe is located less that
10’ from the NGC, no sample conditioning module is required.
1.17.1 Gas Types
The user can select from one of four sample conditioning modules for installations
whose gas samples do not meet the ideal clean and dry conditions. The following
definitions define what is meant by the condition of natural gas to be sampled.
• Clean gas is defined as having no particles larger than one micron and no
more than one milligram of solids per cubic meter of gas.
• Dry gas is defined as having no more than seven pounds of water per million
cubic feet of gas. Gas has less than 0.1 PPM of liquid at the coldest ambient
condition expected at the coldest point in the system. The liquid can be water,
oil, synthetic lubrication, glycol, condensed sample or any other non vapor
contaminate.
Stable gas is a vapor containing less than 0.1 PPM of liquid when vapor is cooled
to 18.3°F (10°C) below the coldest ambient temperature possible at any point in
the system.