Indicator LEDs and operation indication messages
The operation of the relay can be monitored via the HMI by means of LED
indications and text messages on the LCD. On the front panel of the relay there are
three indicator LEDs with fixed functionality:
* Green indicator LED (ready)
* Yellow indicator LED (start/alarm)
* Red indicator LED (trip)
In addition, there are eight programmable LEDs and an indicator LED for front
communication. Refer to the Operator’s Manual for a more thorough presentation.
The indication messages on the LCD have a certain priority order. If different types
of indications are activated simultaneously, the message with the highest priority
appears on the LCD.
The relay provides three different kinds of demand values.
The first value shows the average voltage of all three phase-to-phase voltages
measured during one minute. The value is updated once a minute.
The second value shows the average voltage during an adjustable time range,
ranging from 0 to 999 minutes, with an accuracy of one minute. This value is
updated at the expiration of each time range.
The third value shows the highest one-minute average voltage value measured
during the previous time range. However, if the time range is set to zero, only the
one-minute and the maximum average voltage value is shown. The maximum value
is the highest one-minute mean value since the last reset.
The demand voltage values can be set to zero through serial communication using
SPA parameter V102. The average voltage values are also reset if SPA parameter
V105 is changed or the relay is reset.