Indirect evaporative air cooler with dehumidifier
USD $1,000 - $100,000 /Unit
Min.Order:1 Unit
Hodream Environment Equipment Co., Ltd.
high efficiency liquid desiccant normal temperature dehumidification dryer units
energy saving deep commercial liquid desiccant air conditioning better than desiccant wheel
Entire Heat Recovery Liquid Desiccant Conditioning Type Fresh Air Units
outer rotor centrifugal dehumidifier fan motor liquid desiccant dehumidifier DD03
dehumidifying air 850m3/h and exhaust air 1500m3/h food dehumidifier
Brine solution dehumidifier an industrial dehumidifier with air condtion function
Introduction
This brine solution dehumidifier suits for a whole years climates,summer time or winter time. And it's especially suitable for air conditioning systems with temperature and humidity independent controlled, Enclosed room needs deep dehumidifying where demands a constant temperature and humidity, such as ICU(Intensive care unit), R&D buildings, laboratory, exhibition centers, hotels, apartments, machine room,factories and military.
Application
Specification
Model(TAH-xx) | 10 | 12 | 15 | 20 | 25 | 30 | 40 | ||
Power Source | 3PH-380V-50Hz | ||||||||
Supply Air Rate | m3/h | 10000 | 12000 | 15000 | 20000 | 25000 | 30000 | 40000 | |
Return Air Rate | m3/h | 7000 | 8400 | 10500 | 14000 | 17500 | 21000 | 28000 | |
Fresh Air Rate | m3/h | 3000 | 3600 | 4500 | 6000 | 7500 | 9000 | 12000 | |
Cooling Capacity | kW | 87 | 104 | 130 | 174 | 216 | 260 | 347 | |
Dehumidification | kg/h | 64 | 77 | 96 | 128 | 160 | 192 | 256 | |
Heating | kW | 92 | 111 | 139 | 185 | 231 | 277 | 370 | |
Moisture | kg/h | 24 | 29 | 37 | 49 | 61 | 73 | 98 | |
Power | kW | 18.7 | 21.1 | 26.4 | 34.0 | 41.6 | 52.8 | 70.4 | |
Air supply excess pressure | Pa | 350 | 370 | 350 | 350 | 350 | 350 | 350 | |
Noise | dB(A) | 65 | 66 | 66 | 68 | 70 | 73 | 75 | |
Weight | kg | 2660 | 2956 | 3823 | 4521 | 5263 | 6283 | 7355 | |
Fresh Air Section | |||||||||
Fresh Air Rate | m3/h | 3000 | 3600 | 4500 | 6000 | 7500 | 9000 | 12000 | |
Supply Air Rate | m3/h | 3000 | 3600 | 4500 | 6000 | 7500 | 9000 | 12000 | |
Cooling Capacity | kW | 63 | 75 | 94 | 125 | 156 | 187 | 250 | |
Dehumidification | kg/h | 62 | 74 | 93 | 124 | 155 | 186 | 248 | |
Heating | kW | 41 | 49 | 61 | 81 | 101 | 122 | 162 | |
Moisture | kg/h | 24 | 29 | 37 | 49 | 61 | 73 | 98 | |
Power | kW | 13.8 | 15.8 | 20.1 | 25.8 | 31.3 | 40.5 | 53.9 | |
Compressor Type | Fully Closed Scroll Compressor | ||||||||
Throttle Type | Thermal Expansion Valve | ||||||||
Refrigerant | R407C | ||||||||
Exhaust Fan Type | Outer Rotor Centrifugal Fan | ||||||||
Filter Grade | Primary(G4) | ||||||||
Air exhaust excess pressure | Pa | 170 | 180 | 170 | 180 | 190 | 170 | 430 | |
Weight | kg | 2050 | 2200 | 2650 | 3080 | 3580 | 4350 | 5140 | |
Mixed Air Section | |||||||||
Filter Grade | Primary(G4) | ||||||||
Weight | kg | 100 | 140 | 175 | 195 | 210 | 265 | 320 | |
Cold And hot Coil Section | |||||||||
Cooling Capacity | kW | 24.2 | 29.1 | 36.4 | 48.5 | 60.6 | 72.7 | 96.9 | |
Heating Capacity | kW | 51.9 | 62.2 | 77.8 | 103.7 | 129.7 | 155.6 | 207.5 | |
water inlet/outlet temp. | ℃ | Cold Water:14/19;Hot Water:50/45 | |||||||
cold-water flow | m3/h | 4.2 | 5.0 | 6.2 | 8.3 | 10.4 | 12.5 | 16.6 | |
hot-water flow | m3/h | 8.9 | 10.7 | 13.3 | 17.8 | 22.2 | 26.7 | 35.6 | |
Connecting Pipe | DN40 | DN40 | DN50 | DN50 | DN65 | DN65 | DN80 | ||
Water Resistance | kPa | <60 | |||||||
Weight | kg | 170 | 230 | 320 | 400 | 510 | 610 | 740 | |
Supply Air Section | |||||||||
Fan Type | Belt-driven Double Inlet Centrifugal Fan | ||||||||
Power | kW | 5.2 | 5.6 | 6.6 | 8.7 | 10.8 | 13.0 | 17.3 | |
Weight | kg | 340 | 386 | 678 | 846 | 963 | 1058 | 1155 |
Notes:1.Nominal cooling and dehumidification working conditions: fresh air dry bulb temperature 36℃, relative humidity 65%,; returned air dry bulb temperature 26℃, relative humidity 60%; supply air dry bulb temperature 17℃, wet bulb temperature 16.0℃.
2. Nominal heating and humidification working conditions: fresh air dry bulb temperature -5℃, relative humidity 50%,;returned air dry bulb temperature 20℃, relative humidity 50%; supply air dry bulb temperature 35℃, wet bulb temperature 19.0℃.
3. The above section and setting are only for reference. Pls choose and adjust based on actual project requirement, or provided by customer.
Dimension Drawing
Model(TAH-xx) | 10 | 12 | 15 | 20 | 25 | 30 | 40 | |||
Sectional size W*H (mm) | ||||||||||
W | mm | 1500 | 1500 | 1850 | 1850 | 2300 | 2300 | 2300 | ||
H1 | mm | 2300 | 2300 | 2400 | 2400 | 2500 | 2800 | 3000 | ||
H2 | mm | 1300 | 1500 | 1500 | 1800 | 1800 | 2050 | 2500 | ||
L=L1+L2+L3+L4 | mm | 5770 | 5770 | 6350 | 6450 | 6850 | 7180 | 7280 | ||
Function section size (mm) | ||||||||||
Fresh Air Dehumidification Section | Section Length | L1 | mm | 3300 | 3300 | 3500 | 3500 | 3700 | 3700 | 3800 |
Return Air Outlet One | J | mm | 350 | 400 | 400 | 450 | 450 | 550 | 650 | |
K | mm | 1100 | 1100 | 1500 | 1500 | 1900 | 1900 | 1900 | ||
Fresh Air Outlet | E | mm | 500 | 600 | 600 | 680 | 650 | 800 | 950 | |
F | mm | 700 | 700 | 900 | 900 | 1300 | 1300 | 1300 | ||
Exhaust Air Outlet | C | mm | 200 | 200 | 300 | 300 | 300 | 300 | 400 | |
D | mm | 310 | 350 | 390 | 450 | 450 | 450 | 627 | ||
Mixing section | Section Length | L2 | mm | 420 | 420 | 500 | 600 | 600 | 730 | 730 |
Return Air Outlet Two | M | mm | 320 | 320 | 400 | 500 | 500 | 630 | 630 | |
N | mm | 1000 | 1250 | 1250 | 1600 | 1600 | 2000 | 2000 | ||
Cooling Coiler Section | Section Length | L3 | mm | 750 | ||||||
Cold and hot water pipe Outlet | DN1 | mm | DN40 | DN40 | DN50 | DN50 | DN65 | DN65 | DN80 | |
DN2 | mm | DN40 | DN40 | DN50 | DN50 | DN65 | DN65 | DN80 | ||
Supply Air Section | Section Length | L4 | mm | 1300 | 1300 | 1600 | 1600 | 1800 | 2000 | 2000 |
Supply Air Outlet | A | mm | 485 | 550 | 605 | 675 | 740 | 785 | 950 | |
B | mm | 412 | 466 | 532 | 580 | 650 | 700 | 780 |
Note:As our products are improved continuously, specifications in the tables are subject to change without notice.