Water flow is 10m3 per hour Round Counter Water tower for cooling water system
USD $285 - $385 /Set
Min.Order:1 Set
Wenzhou Sanhe Refrigeration Equipment Co., Ltd.
With water pump Round Counter closed cooling water tower selling
Water flow is 20m3 per hour Round Counter Small water cooling tower price list
Round Counter Cooling water tower plant for water chiller system
water flow is 30m3 per hour Round Water cooling tower system
40T Round cooling water tower working with water chiller system
Water flow is 10m3 per hour Round Counter Water tower for cooling water system
I. Description of Water tower :
Cooling tower is mainly applied to air conditioning cooling system , cooling series , plastic , leather , power generation, and steam turbine , aluminum processing , air compressor , industrial cooling tower , cooling for industrial production or refrigeration technology process.
Water tower for installing
II. Working condition of Water tower:
Water inlet temperature:80°C
Water outlet temperature:50°C
Wet bulb temperature:28°C
Dry bulb tem peranure:31.8°C
Atmospheric pressure:9.94×10000Pa
Material: glass fiber reinforced plastic (GFRP)
Water flow : is from 8m3h to 1000m3/h
III.Technology parameter of Water tower :
Model
| Water flow | Fan diameter | Theoretical air | Motor power | Tower height | Tower diameter | Weight |
(m3/h) | (mm) | (m3/h) | (kw) | (mm) | (mm) | (kg) | |
XTH-8 | 8 | 584 | 4500 | 0.18 | 1560 | 930 | 64 |
XTH-10 | 10 | 584 | 5700 | 0.18 | 1670 | 1000 | 85 |
XTH12 | 12 | 760 | 6800 | 0.37 | 1700 | 1100 | 94 |
XTH-15 | 15 | 760 | 9100 | 0.37 | 1780 | 1250 | 124 |
XTH-20 | 20 | 760 | 11300 | 0.37 | 1780 | 1400 | 158 |
XTH-25 | 25 | 760 | 15000 | 0.55 | 1780 | 1400 | 174 |
XTH-30 | 30 | 884 | 17000 | 0.75 | 1960 | 1620 | 185 |
XTH-40 | 40 | 884 | 21000 | 0.75 | 2010 | 1740 | 192 |
XTH-50 | 50 | 884 | 23000 | 1.1 | 2010 | 1840 | 215 |
XTH-60 | 60 | 1190 | 28000 | 1.1 | 2400 | 2200 | 412 |
XTH-70 | 70 | 1190 | 33000 | 1.5 | 2530 | 2200 | 476 |
XTH-80 | 80 | 1470 | 45000 | 2.2 | 2680 | 2500 | 680 |
XTH-90 | 90 | 1470 | 48000 | 2.2 | 2710 | 2500 | 730 |
XTH-100 | 100 | 1470 | 50000 | 2.2 | 2820 | 2900 | 776 |
XTH-125 | 125 | 1800 | 57000 | 4 | 3130 | 3300 | 954 |
XTH-150 | 150 | 1800 | 70000 | 4 | 3350 | 3300 | 1062 |
XTH-175 | 175 | 1800 | 85000 | 4 | 3670 | 3600 | 1468 |
XTH-200 | 200 | 1800 | 99000 | 4 | 3900 | 4000 | 1797 |
XTH-225 | 225 | 2400 | 113000 | 5.5 | 4165 | 4500 | 1987 |
XTH-250 | 250 | 2400 | 142000 | 5.5 | 4290 | 4500 | 2370 |
XTH-300 | 300 | 3000 | 171000 | 7.5 | 4435 | 4900 | 2495 |
XTH-350 | 350 | 3000 | 210000 | 11 | 4735 | 5300 | 2702 |
XTH-400 | 400 | 3400 | 228000 | 11 | 4820 | 6100 | 3592 |
XTH-450 | 450 | 3400 | 285000 | 15 | 4820 | 6100 | 3741 |
XTH-500 | 500 | 3700 | 342000 | 15 | 5145 | 6800 | 4276 |
XTH-600 | 600 | 3700 | 400000 | 18.5 | 5145 | 6800 | 4457 |
XTH-700 | 700 | 4200 | 456000 | 22 | 5732 | 8000 | 6167 |
XTH-800 | 800 | 4200 | 570000 | 22 | 5732 | 8000 | 6445 |
Water towers in our working shop photo
Water cooling towers ready for sending to Peru
We're on the fair