it enables the use of current-limiting circuit-breakers only at levels hierarchically
lower down the chain; the other circuit-breakers have to be capable of
withstanding the thermal and electro-dynamic stresses related to the passage
of the fault current for the intentional time delay. Selective circuit-breakers,
often air type, have to be used for the various levels to guarantee a sufficiently
high short-time withstand current;
• the duration of the disturbance induced by the short-circuit current on the
power supply voltages in the zones unaffected by the fault can cause problems
with electronic and electro-mechanical devices (voltage below the
electromagnetic releasing value);
• the number of discrimination levels is limited by the maximum time that the
network can stand without loss of stability.
The following example shows a typical application of time discrimination obtained
by setting differently the tripping times of the different protection devices.
his type of coordination is implemented by means of a dialogue between
current measuring devices that, when they ascertain that a setting threshold
has been exceeded, give the correct identification and disconnection only of
the zone affected by the fault.
It is available with the circuit-breakers of Emax series only.
In practice, it can be implemented in two ways:
• the releases send information on the preset current threshold that has been
exceeded to the supervisor system and the latter decides which protective
device has to trip;
• in the event of current values exceeding its setting threshold, each protective
device sends a blocking signal via a direct connection or bus to the protective
device higher in the hierarchy (i.e. upstream with respect to the direction of
the power flow) and, before it trips, it makes sure that a similar blocking signal
has not arrived from the protective device downstream; in this way, only the
protective device immediately upstream of the fault trips.