Acrel AC Residual current transducer input:AC 0-1A output:DC 0-5V/0-10V CT diameter 50mm true RMS current sensor BA50L-AI/V-T
Negotiable
Min.Order:1
Item | Description | ||||||
Power Supply | Voltage | DC 24V or DC 12V | |||||
Consumption | ≤ 1W | ||||||
Insulation Resitance | >100 MΩ | ||||||
Withstand Strength | Between input/output, power supply 2.0 kV/1min, 50Hz | ||||||
Temperature Coefficient | ≤200 PPM/℃,under -10℃~+55℃ | ||||||
Environment | Temperature | Working: -10℃~+55℃, Storage: -25℃~+70℃。 | |||||
Humidity | ≤95% RH, No condensation, without corrosive gas | ||||||
Altitude | TS35 guide rail or fiexed on cabinet with screws |
Paramters | Value&Description | ||||||
Accuracy Class | class 0.5, class 0.2 | ||||||
Input | Nominal Value | AC 0~1A | |||||
Overload | continuous overload 1.2×Ib (1.2 times of nominal value); instant overload 10×Ib/1s (10 times of nominal value for 1 second) | ||||||
Absorbed Power | ≤1 VA | ||||||
Frequency response | 25Hz~800Hz (average); 25Hz~5000 Hz(true RMS), specialized for power frequency scenario | ||||||
Output | Nominal Value | DC 0~5V, DC 0~10V etc. | |||||
Load Resistance | ≤500 Ω with current output; ≤1000 Ω with voltage output | ||||||
Response Time | ≤ 350 ms (average); ≤100 ms (true RMS) | ||||||
Measuring Method | True RMS measurement |