High Tension Composite Suspension Insulator , 10kv Overhead Line Insulators
USD $5.00 15.00 - $5.00 15.00 /Square Meter
Min.Order:1 Square Meter
Composite Line post Insulator , 252kV / 220kV Station Post Insulators
110 kV Polymer Line Post Type Insulator Safety For Power Substations
66kV Polymer Station Post Insulators Flameproof High Pollution Resistance
35kV Line Post Insulator Minimum Creepage Distance 1320mm For Substations
Composite Line Post Insulator , IEC 61952 20kV Substation Insulator
ANSI 10 kV / 11 kV Post Insulator Creepage Distance 380mm For Substation
High Tension Composite Suspension Insulator , 10kv Overhead Line Insulators
Specifications:
Dimensions and Characteristics of 10kV(12kV)composite Suspension Insulator
Figure. No | Model | Rated Voltage | Specified Mechanical Load | Coupling Size | Section Length |
Insulating length |
Minimum Creepage | Full-Wave Impulse Withstand Voltage (Peak) |
1 Min Wet Power Frequency Withstand Voltage |
Weight (for Reference) |
kV |
kN |
H mm |
h mm |
L mm |
≥ kV |
≥ kV |
kg |
|||
1.15-1 | FXBW-10/70-WT-A | 10 | 70 | 16 | 340±5 | 163 | 400 | 95 | 60 | 1.5 |
1.15-2 | FXBW-10/70-DT-A | 10 | 70 | 16 | 343±5 | 163 | 400 | 95 | 60 | 1.3 |
1.15-3 | FXBW-10/70-WD | 10 | 70 | 16 | 322±5 | 159 | 415 | 95 | 60 | 1.3 |
1.15-4 | FXBW-10/70-DT-B | 10 | 70 | 16 | 312±5 | 159 | 415 | 95 | 60 | 1.1 |
1.15-5 | FXBW-10/70-WT-B | 10 | 70 | 16 | 319±5 | 159 | 415 | 95 | 60 | 1.2 |
1.15-6 | FXBW-10/70-UD-A | 10 | 70 | / | 318±5 | 159 | 415 | 95 | 60 | 1.2 |
1.15-7 | FXBW-10/70-UD-B | 10 | 70 | / | 360±5 | 158 | 600 | 95 | 60 | 1.4 |
1.15-8 | FXBW-10/70-UD-C | 10 | 70 | / | 365±5 | 163 | 400 | 95 | 60 | 1.4 |
1.15-9 | FXBW-10/70- WT -C | 10 | 70 | 16 | 296±5 | 163 | 460 | 95 | 60 | 1.4 |
1.15-10 | FXBW-10/70- TT -A | 10 | 70 | 16 | 296±5 | 163 | 460 | 95 | 60 | 1.4 |
1.15-11 | FXBW-10/70- PT -A | 10 | 20 | 16 | 375±5 | 163 | 400 | 95 | 60 | 1.3 |
Description:
1, 10kV tension suspension insulators are widely used in overhead transmission lines and substations
2, Dead end fittings are up to the requirements from the clients, usually we use ball, socket, tongue, clevis for tension insulators with forged steel or cast steel. The dimensions and coupling size can be exactly according to the specification requirements from the utilities.
3, The silicon rubber color of the insulators are also up to the requirements from the clients and all the silicon rubber materials past 5000 hours aging test silicon content test and hydrophobicity test.
4, ECR core rods are used in all the insulators, so we can guarantee a very good mechanical strength and anti-acid pollution performance for the insulators.
5, All our insulators were type tested and design tested in accordance with IEC61109, maximum RIV is 100µV when tested at 1MHz and10% over nominal line ground voltage for indicated system voltage.
6, All the 10kV tension suspension insulators are without corona ring
Applications:
1, 10kV overhead transmission power lines.
2, 10kV substations
3, 10kV distribution lines
Advantages:
This kind of products have the following characters and advantages:
1) The silicon rubber rain shed, designed according to the aerodynamics principle, use the whole-moulding method, to make sure the validity of total creepage distance under every climate and nasty conditions, as well as improved the pollution discharge of the insulators.
2) The fiber rod uses the ECR high-