Digital Temprature Controller
Negotiable /Piece
Min.Order:1 Piece
AMBETRONICS ENGINEERS PRIVATE LIMITED
Digital Temprature Controller
FEATURES:
APPLICATIONS:
TECHNICAL SPECIFICATIONS: | ||||
Inputs | Range | Resolution | Accuracy | |
Minimum | Maximum | Normal | Full Scale | |
RTD PT 100 (3 WIRE) | -200°C | 400.0°C | 0.1 | ±0.25% |
J Type (Fe - CON) | -50.0°C | 600.0°C | 0.1 | ±0.25% |
K Type (Cr- AL) | -50.0°C | 500.0°C | 0.1 | ±0.25% |
K Type (Cr- AL) | -50°C | 1200°C | 1 | ±0.25% |
R Type (PT 13 % RH / PT), S TYPE (PT 13 % RH / PT) | 0°C | 1750°C | 1 | ±0.25% |
T Type (Cu / CON) | -50°C | 400.°C | 0.1 | ±0.25% |
N Type, E Type (Cr / CON) | 0°C | 1300°C | 1 | ±0.25% |
B Type (PT 6 % RH / PT 30 %RH) | 400°C | 1820°C | 1 | ±0.25% |
4~20 Ma / 0 ~20 mA | -999 | 9999 | Programmable by User | ±0.25% |
Voltage (0 ~1 VDC / 0~ 10 mVDC) | -999 | 9999 | ±0.25% | |
Compensation | Automatic Cold Junction Compensation for all Thermocouples. Automatic Wire length for long wire RTD Inputs | |||
Sensor Break | Temperature Sensor Break OR Sensor Open, Display Shows 'oPEn' indication. Under Range 'Undr' Over Range 'ouEr' indication for 4~20mA & 0~10 VDC. | |||
Display | 4 Digits of 13 mm Height L.E.D. for process value display. 4 L.E.D.s for RL1, RL2,TX, RX | |||
Setting | By 3 Keys on front Panel | |||
Set Point | Two Independents set point with individual relay output with hysteresis settable. Programmable latch OR non Latch facility for both relay output. | |||
Control Action | High & Very High. High & Low. Low & very Low Programmable by User. | |||
Relay Output | 1 NO/C/NC Relay Contact rated 230 V/5A for Relay 1 (RL1) & Relay 2 (RL2) | |||
Supply | 230 VAC +/-10%, 110VAC +/-10%, 24 VDC | |||
Mounting | Panel Mounting / Wall Mounting type for Flameproof Model | |||
Dimension | 96 (W) x 48 (H) x 120 (D) in mm OR 72 (W )x 72 (H) x 120 (D) in mm | |||
Cutout | 92 (W) x 44 (H) in mm OR 68 (W) x 68 (H) in mm | |||
Cabinet | ABS Plastic | |||
Optional | a)Isolated RS485 serial port with MODBUS RTU Protocol output for PC interface. Powerful SCADA software is available. b)Isolated 4 ~20mA / 0~1 VDC retransmission programmable output for recorder or PLC proportional to Selective range. c)Flameproof Version is available on request for hazardous application. | |||
Weight | 1 Kg. |