Middle Voltage MV 15KV COPPER CONDUCTOR XLPE INSULATED STEEL TAPE ARMORED CABLE
USD $0.058 - $0.285 /Meter
Min.Order:500 Meters
Zhengzhou Jinyuan Wire And Cable Co., Ltd.
Middle Voltage MV 15KV COPPER CONDUCTOR XLPE INSULATED STEEL TAPE ARMORED CABLE
8.7/15kV CU/XLPE/STA/PVC(or PE) Power Cable
1. XLPE CABLE Description
Construction: Compacted stranded circular copper conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC inner covering as armoring bedding, double galvanized steel tape armored, PVC or PE outer sheath.
Chinese Type | Description | Core qty | Conductors range |
YJV22 | Copper conductor, XLPE insulation, Steel Tape Armored, PVC outer sheath Power Cable | 1 or 3 | 25~800mm2 |
YJV23 | Copper conductor, XLPE insulation, Steel Tape Armored, PE outer sheath Power Cable | 1 or 3 | 25~800mm2 |
ZA-YJV22 ZB-YJV22 ZC-YJV22 | Copper conductor, XLPE insulation, Steel Tape Armored flame-retardant Power Cable | 1 or 3 | 25~800mm2 |
WDZA-YJY23 WDZB-YJY23 WDZC-YJY23 | Copper conductor, XLPE insulation, Steel Tape Armored Low Smoke Halogen Free or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable | 1 or 3 | 25~800mm2 |
2. XLPE CABLE Operating Characteristics
Rated voltage U0/U(Um): 8.7/15(17.5)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the “highest system voltage” for which the equipment may be used.
Max. permissible continuous operating temperature of conductor: 90 °C
Max. temperature of conductor during short-circuit (5s max. duration) shall not exceed: 250 °C
The ambient temperature under installation should not be lower than: 0 °C
The bending radius of cable is recommended as following:
For single core cable: not less than 20 times of the diameter of cable
For three core cable: not less than 15 times of the diameter of cable
3. XLPE CABLE Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel or in cable trench, unable to bear external mechanical force.
Single core cable in magnetic duct is not permissible.
Main technical data of 8.7/15KV, three cores, Copper conductor, XLPE insulated, double galvanized steel tape armored and PVC or PE sheath cable
Size | Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 200C (Ω/km) |
3x25mm2 | 4.5 | 0.10 | 0.5 | 2.5 | 51.3 | 0.727 |
3x35mm2 | 4.5 | 0.10 | 0.5 | 2.6 | 53.7 | 0.524 |
3x50mm2 | 4.5 | 010 | 0.5 | 2.7 | 56.5 | 0.387 |
3x70mm2 | 4.5 | 0.10 | 0.5 | 2.8 | 60.5 | 0.268 |
3x95mm2 | 4.5 | 0.10 | 0.5 | 2.9 | 64.4 | 0.193 |
3x120mm2 | 4.5 | 0.10 | 0.5 | 3.0 | 67.9 | 0.153 |
3x150mm2 | 4.5 | 0.10 | 0.5 | 3.1 | 71.6 | 0.124 |
3x185mm2 | 4.5 | 0.10 | 0.5 | 3.3 | 75.7 | 0.0991 |
3x240mm2 | 4.5 | 0.10 | 0.5 | 3.4 | 81.4 | 0.0754 |
3x300mm2 | 4.5 | 0.10 | 0.8 | 3.6 | 87.6 | 0.0601 |
3x400mm2 | 4.5 | 0.10 | 0.8 | 3.9 | 95.4 | 0.0470 |
MV XLPE CABLE