2. Technical Parameter
SPD Type |
DK-20 2P 2 Poles Single Phase 275V AC Power SPD Protector Surge Protection Device
|
Applicable Power Supply System |
TT, TN, IT Power Supply System |
Maximum Continuous Operating Voltage Uc |
AC 385V |
Nominal Discharge Current (8/20µs) |
10kA |
Maximum Discharge Current (8/20µs) |
25kA |
Voltage Protection Level Up |
≤1.5kV |
≤1.1kV(8/20µs,5kA) |
|
Leakage Current |
≤20uA |
Respond Time tA |
≤25ns |
Indication Method |
Indication Window, Turn Red When Malfunction |
Remote Alarm Function |
Optional |
Maximum Connection Wire Range |
BVR 25mm2 |
Method of Installation |
35mm Din Rail Mounted |
Material of Shell |
PC |
Flame Retardant Rating of Outer Shell |
UL94-V0 |
Protection Level of Outer Shell |
IP20 |
Working Temperature |
–25~+70℃ |
Relative Humidity |
≤95%RH |
3. Item Number
Item Series |
Protection Mode |
Installation Location |
Dimension(mm) |
Item No. |
DK-20 |
L-PE, N-PE(2P) |
Low-voltage Single Phase Power Distribution Cabinet |
36*91*66mm |
DK-20 2P |
L-N-PE(1+1P) |
DK-20(1+1) |
|||
L-PE, N-PE(4P) |
Low-voltage Three Phase Power Distribution Cabinet |
72*91*66mm |
DK-20 4P |
|
L-N-PE(3+1P) |
DK-20(3+1) |
4. Application Scope
It can be installed in the low voltage power distribution cabinet/box of buildings, to protect all kinds of power equipment in the single (three) phase power distribution system between LPZ1 and LPZ2. Such as:
1) Low voltage general electricity cabinet and or distribution board of buildings.
2) Outdoor electricity cabinet/distribution box.
3) Applicable power supply system: TT, TN, IT.
5. External View
6. Installation and Caution
1) DK-20 modular surge protective device(SPD) can be installed in any place of the single phase AC power line, and mostly be installed in power distribution boxes, power switches and sockets. It shall be connected with the power line in parallel, and shall adopt Kevin Connection, so as to lower the residual voltage.
2) Strip away the surface rubber of input and output terminal, and expose the copper core. Insert the copper core into the hole of the SPD, and make it firm with a screwdriver.
3) The cross-section of the grounding conductor connected with the module SPD indicating alarm shall be at least 16mm2, and the lead wire of the grounding conductor shall be shorter than 1m, and the shorter the better.
Q1: What’s your advantages?
A2: Yes, OEM and ODM are both acceptable.
A3: Of course, sample order and small order are acceptable, especially for new customers under certain condition.
A4: For new customers, there is a small discount, but when the value of the order is increased, we will provide a larger discount. For previous customers, we are happy to provide a discount for your loyalty.
Q5: What's the MOQ for OEM?
A5: 5 pcs for sample order, 200 pcs for mass order.
Q6: How about warranty?
A6: Normally it is 2 years. Also it may depend on the actual situation.
Q7: What's your delivery time?
A7: 3-15 days after receipt of the payment(depend on the quantity), please contact us for final confirmation.