SFB199 Zinc Oxide Arrester Tester
Negotiable /Piece
Min.Order:1 Piece
Contact US
Email:info@launch-electric.com
Introduction
The instrument is used to test specific parameters on field or in laboratory for zinc oxide arrester. It is widely used in on-site inspection (live testing) and laboratory tests (power cut overhauling). It is in line with national standards in DL474.5-92 On-site Insulation Test Implementation Guidelines- Arrester Test.
Technical Parameters
Test and measurement range
Full current (peak): 0~20MA
Third harmonic current :0~20MA
Resistive current (peak): 0~20MA
Capacitive current (peak): 0~20MA
Arrester efficacy: 0~8W
Beside above measurements, voltage and full current waveforms could also be displayed.
Measurement error:
Test voltage: ±5%
Full current: ±2%
Resistive current: ±5%
Capacitive current:±5%
Arrester power dissipation: ±5%
Input signal
Voltage signal(LV side of PT): AC 5~200V
Current signal: AC 0~20mA
Power Supply: AC, 220V±10%, 50Hz