Electric Transmission Line Cross Arm Insulator Composite 22kV / 24kV
USD $15.00 - $ 65.00 /Set
Min.Order:1 Set
35kV / 33kV Transmission Line Post Insulator , Grey Polymer Post Insulator
2250mm Creepage Distance In Line Post Insulator Polymeric 66kV / 69kV
Substation Post Transmission Line Insulator Composite 110 Kv High Flexibility
Flexible Polymer Pin Insulator 33kV High Anti - Acid Pollution Performance
20kV Small Volume Polymer Pin Insulator , Safety Distribution Insulators
15kV ECR Solid Core Insulator Polymer Light Weight For Electric Line
Electric Transmission Line Cross Arm Insulator Composite 22kV / 24kV
Specifications:
Dimensions and Characteristics of 22kV line post insulator for Transmission Line
Figure. No | Model | Rated Voltage | Specified Cantilever Load | Section Length |
Insulating length |
Minimum Creepage | Full-Wave Impulse Withstand Voltage (Peak) |
1 Min Wet Power Frequency Withstand Voltage |
Weight (for Reference) |
kV |
kN |
H mm |
h mm |
L mm |
≥ kV |
≥ kV |
kg |
||
6.4 | FZSW-22/6 | 22 | 6 | 337+5 | 160 | 600 | 150 | 50 | 4.9 |
6.4 | FZSW-24/8 | 22 | 8 | 337+5 | 160 | 600 | 150 | 50 | 4.9 |
Description:
1, 22kV,24kV Line Post Insulators are widely used in power transmission lines.
2, Dead end fittings are up to the requirements from the clients, usually we use different flanges for post insulators with forged steel or cast steel. The dimensions and coupling size can be exactly according to the specification requirements from the utilities.
3, The silicon rubber color of the insulators are also up to the requirements from the clients and all the silicon rubber materials past 5000 hours aging test silicon content test and hydrophobicity test.
4, ECR core rods are used in all the insulators, so we can guarantee a very good mechanical strength and anti-acid pollution performance for the insulators.
5, All our insulators were type tested and design tested in accordance with IEC61952, maximum RIV is 100µV when tested at 1MHz and10% over nominal line ground voltage for indicated system voltage.
6, All the Line Post Insulators with the voltage lower than 110kV are not supposed to use corona ring.
All the Line Post Insulators with the voltage equal to or higher than 110kV but lower than 220kV are supposed to use one corona ring at the line end.
All the Line Post Insulators with the voltage equal to or higher than 220kV are supposed to use two corona rings at both sides.
Applications:
1, Usually used in 22kV,24kV Electric Transmission Power Lines