Protection Relay Test Set K1030i
Negotiable /Piece
Min.Order:1 Piece
Kingsine Electric Automation Co., Ltd.
In-house and field test, Laptop is unnecessary!
With microprocessor& LCD screen, no matter you are doing in -house or field testing, Laptop is unnecessary .Besides, the powerful & complete software helps you more easy!
1. Adopts 6.4 large LCD screen, and provided with VGA video interface, making it available to connect to projector for training;
2. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
3. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A(Poleless and adjustable);
4. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
5. Function of transducer and energy meter testing (optional function);
6. Adopt Smart and stable Window CE embedded system. Windows has the advantage of small application program with fast speed, which overcomes the problem of bad stability, easy-damage hardware, and virus of Windows 98/2000/XP;
7. Use high-speed CF card as the storage, more stable, anti-shock compared with ordinary hardware, so works more reliable.
Main specifications:
Voltage generators |
||
Setting Range |
4-phase AC (L-N) |
4 x 0 ... 300 V |
2-phase AC (L-L) |
2 x 0 ... 600 V |
|
Power |
4-phase AC (L-N) |
4 x 110VA, at 0 ... 300 V |
2-phase AC (L-L) |
2 x 220VA, at 0 ... 600 V |
|
Accuracy |
<0.07% reading + 0.03% range guaranteed at 0-300V <0.04% reading + 0.01% range typical at 0-300V |
|
Resolution |
1mV |
|
Current generators |
||
Setting Range |
3-phase AC (L-N) |
3 x 0 ... 30 A |
1-phase AC (2L -N) |
1 x 0 ... 60 A |
|
1-phase AC (3L-N) |
1 x 0 ... 90 A |
|
Power |
3-phase AC (L-N) |
3 x 150 VA , at 0 ... 30A Max 250VA, with the other current channels unload |
1-phase AC (2L -N) |
1 x 300VA, at 0 ... 60A Max 450VA, with the other current channels unload |
|
1-phase AC (3L-N) |
1 x 900 VA |
|
Accuracy |
<0.14% reading + 0.06% range guaranteed at 0-40A <0.05% reading + 0.02% range typical at 0-40A |
|
Resolution |
1mA |
|
Generators, general |
||
Frequency |
Range |
0 ... 1000 Hz |
Accuracy / drift |
Error < 0.001Hz at 10 ... 65Hz, Error < 0.01Hz at 65Hz...450Hz Error < 0.02Hz at 450Hz...1000Hz |
|
Resolution |
0.001Hz |
|
Phase |
Range |
- 360° ... +360° |
Accuracy / drift |
Error < 0.2 ° |
|
Resolution |
0.1° |
|
|