K68i Protection Relay Test Set
Negotiable /Piece
Min.Order:1 Piece
Kingsine Electric Automation Co., Ltd.
The most-effective solution for relay testing!
With all in one design, able to test most of Relays by manual or automation!
Software Features:
1. Able to test most of Relays by manual or automation: Voltage relays, Current relays, Frequency relays, Power relays, Impedance relays, Harmonic relays, Distance relays etc;
2. With self housing-grounding-detecting function, the software interface can show whether the housing well grounding or not, effectively ensure the safety of testing.
Hardware Features:
1. All-in-one design relay tester with 6.4 inches LCD display;
2. 4 Phase AC Voltage Sauce and 3 phase AC current sauce can be output together, even the Range, Phase, Frequency can be set independently;
3. Max AC voltage can reach 300V each phase, Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A (Poleless and adjustable);
4. Offer different type of computer port: USB port, RJ45 port, VGA Video Port , USB / RJ45 ports convenient for data transfer, VGA Video Port can connect to projector and easy for study and training;
5. Super long life Rotary encoder + Functional keyboard.
Technical Data of K68
Voltage generators |
||
Setting Range |
4-phase AC (L-N) |
4 x 0 ... 300V |
2-phase AC (L-L) |
2x 0 ...600 V |
|
Power |
4-phase AC (L-N) |
4 x110VA, at 0 ...300 V |
2-phase AC (L-L) |
2 x 220VA, at 0 ...600 V |
|
Accuracy |
<0.07% reading + 0.03% range guaranteed at 0-300V <0.04% reading + 0.01% range typical at 0-300V |
|
Resolution |
1mV |
|
Current generators |
||
Setting Range |
3-phase AC (L-N) |
3 x 0 ... 35 A |
1-phase AC (3L-N) |
1 x 0 ...105 A |
|
Power |
3-phase AC (L-N) |
1x 450VA, at 0 ... 35A |
1-phase AC (3L-N) |
1 x 1000VA, at 0 ...105A |
|
Accuracy |
<0.14% reading + 0.06% range guaranteed at 0-35A <0.05% reading + 0.02% range typical at 0-35A |
|
Resolution |
1mA |
|
Generators, general |
||
Frequency |
Range |
0 ... 1000 Hz |
Accuracy / drift |
Error < 0.001Hz at 10 ... 65Hz, Error < 0.01Hz at 65Hz...450Hz Error < 0.02Hz at 450Hz...1000Hz |
|
Resolution |
0.001Hz |
|
Phase |
Range |
- 360° ... +360° |
Accuracy / drift |
Error < 0.2 ° |
|
Resolution |
0.1° |
|
Time |
Range |
0 ... 999,999.999s |
Accuracy / drift |
Error<1ms |
|
DC generators |
||
Voltage ranges |
0 ... 300V/180VA |
|