Diesel Generator Set Data
Manufacturer: Jiangsu Starlight Generating Equipments Co.,Ltd
Set Type: XG-300GF
Standby Power: 300KW/375KVA
Prime Power: 273KW/341KVA
Rated Current: 491(A)
Rated Frequency: 50(Hz)
Start-up time: 5~6(s)
Power Factor: 0.8(Lag)
Rated Voltage: 400/230(V)
Standard Features
Engine:VOLVO TAD1343GE
Radiator 50℃ max
Fans are driven by belt, with safety guard
24V charge alternator
Dry type air filter, fuel filter, oil filter
Alternator: single bearing alternator
IP23, insulation class H/H
Main line circuit breaker
Standard control panel
Absorber
Muffler
User manual
Diesel Engine Data
Manufacturer: VOLVO
Model: TAD1343GE
Standby/Prime Power: 355KW/323KW
Rated Speed: 1500(r/min)
Cycle: 4 stroke
Cylinder Arrangement: 6 in line
Displacement: 13L
Bore and Stroke: 131*150(mm)
Compression Ratio: 18.1:1
Governor Type: Electronic
Start battery voltage: 24V DC
Air Intake System
Air Intake System: Turbo, Air/Air Cooling
Max Intake Restriction: 5kpa
Burning Capacity: 27m3/min
Air Flow: 408 m3/min
Exhaust System
Exhaust Gas Flow: 60m3/min
Exhaust Temperature: 420℃
Max Back Pressure: 10kPa
Fuel System
Fuel System: Elec. Injection, Elec. Fuel System
100%( Prime Power) Load: 198g/kwh
50%( Prime Power) Load: 213g/kwh
Oil System
Total Oil Capacity: 35L
Oil Consumption: ≤0.04L/h
Engine Oil Tank Capacity: 30L
Oil Pressure at Rated RPM: 370-520kPa
Cooling System
Cooling Way: Water-cooled
Total Coolant Capacity: 44L
Thermostat: 82-92℃
Max Water Temperature: 107℃
Alternator Data
Manufacturer: STARLIGHT/STAMFORD/SIEMENS/MARATHON/ENGGA/KEPU
Excitation Mode: Brushless and self- exciting
Number of phase and Access Act: 3-phase 4-wire
Connecting Type: “Y” type connecting
Alternator Capacity: 375KVA
Alternator Efficiencies: 95%
Overload: (PRP)110% load can run 1h
Protection Level: IP22-IP23
Insulation Class, Temperature Rise: H/H
Telephone Influence Factor (TIF): <50
THF: <2%
Voltage Regulation, Steady State: ≤±1%
Air Cooling Flow: 0.8m3/s
Altitude: ≤1000m