3 phase in 3 phase out ups 60kva
USD $1,979 - $3,675 /Piece
Min.Order:1 Piece
Shenzhen Must Solar Power Co., Ltd.
3 phase in 3 phase out ups 60kva
1. Features
1. Pure sine wave output, true online double conversion
2. Wide input voltage range
3. Can be set to ECO mode
4. With EPO function
5. Can be with 100% unbalance load
6. Adopt the fourth layer PCB, and SMD technology
7. Sixth generation IGBT, much higher efficiency, lower temperature, more reliable
8. Full protection, overload, over voltage, short circuit, over temperature etc
9. Cold start
10. Generator compatible
11. With RS232 and RS485 standard collocate,
12. Option SMMP and dry contact connection
13. Option battery manage function
Nice interface design, LCD display the UPS operating status.
Built in control board design, have on need of any adjustment, easy to maintenance.
Overload protection: When overload, setting to auto-transfer, Overload detection and reset,
if overload vanish, auto-transfer to UPS.
Soft start-up protection: When turn-on ups or after turn-off discharge restoration powersupply for ups, avoid transient varying output.
Double reserve power supply system, operation reliability, to ensure power supply or precision equipments.
RS232 communication interface, provide intelligent supervisory software to ups.
The card insertion add-on SNMP(option), support remote supervisory for network.
2. Pictures
3. Specifications
Type | MD-10 | MD-15 | MD-20 | MD-30 | MD-40 | MD-50 | MD-60 |
(KVA) | 10 | 15 | 20 | 30 | 40 | 50 | 60 |
Input capacity(A) | 20 | 30 | 40 | 60 | 80 | 101 | 121 |
Working | 6pulse (12 pulse option)rectifier | ||||||
Phase | Three phase +N+G | ||||||
Voltage | 380VAC±25% | ||||||
Frequency | 50Hz±5%,60Hz±5% | ||||||
THD | <5% | ||||||
Soft start | 0~100% 5S | ||||||
Output voltage | 405/432VDC | ||||||
Set the DC voltage | 378~432VDC(set them by our engineer) |
Type | MD-10 | MD-15 | MD-20 | MD-30 | MD-40 | MD-50 | MD-60 |
MAX current discharge(A) | 27.6 | 42.5 | 55 | 82 | 108 | 135 | 162 |
Battery type | maintenance-free lead acid battery | ||||||
Battery | 30~32pcs | ||||||
DC voltage | 360/384VDC | ||||||
Float voltage | 360/432VDC (once of three months charge ,charge votage 435/464VDC) | ||||||
Charge power | Rated power@ 20%(automatically change follow the batteries ) |
Type | MD-10 | MD-15 | MD-20 | MD-30 | MD-40 | MD-50 | MD-60 |
Rated power | Capacity × 0.8(KW) | ||||||
Phase | Three phase +N+G | ||||||
Voltage | 220/380VAC±1%(state load), | ||||||
Frequency | 50Hz±0.5%,60Hz±0.5%(with battery) | ||||||
Output frequency | <±0.5%(no in phase) | ||||||
Input frequency | 50Hz±5% | ||||||
Crest factor | 3:1 | ||||||
Wave | Sine wave | ||||||
Output waveform | Sine wave ,linear load<3%;non-linear load<5% | ||||||
Dynamic characteristics | <±5% (0←→ 100%load) | ||||||
Recover time | <10ms | ||||||
Overload | 125% 1min,150% 1S | ||||||
Inverter efficiency | ≥95% (with100% load) |
5. Applications
MD-C series is three phase in and out online UPS, mainly for the IT device, date center, precision Instrument, bank ,Intelligent equipment, Securities electric factory ,traffic, industry and so on