1. Features
2. Data Sheet
Output | C6KVA/C6KS | C10KVA/C10KS |
Rated Power | 6000VA/4200W | 10000VA/7000W |
Output Voltage | 208VAC/220VAC/230VAC/240VAC | |
Voltage Waveform | Pure Sine wave | |
Crest Factor | 3:1 | |
Output Frequency (Synchronized- Mains) | 46~54Hz or 56Hz - 64Hz (Line mode) 50/60HZ/ ±0.05Hz( Battery mode) | |
Regulation(Nominal) | ±1% | |
Regulation(Battery mode) | ±1% | |
Transfer time | AC to DC :Zero Inverter to Bypass: Zero | |
Over current protection | Line Mode:10min@100%~130%;Battery Mode:30s@100%~130% | |
Outlet | Hard Wiring with Terminal Block | |
Harmonic Distortion | ≤2%THD(Linear Load);≤5%THD(Non-Linear Load) |
2.Input
Nominal Voltage | 160~300VAC@full load (110~300VAC@half load) |
Input Frequency | 46~54Hz / 56~60Hz |
Efficiency | 90% (AC mode) 90%(Battery Type) |
Noise Filtering | Full time EMI/RFI filtering |
Over current protection | by AC fuse or by re-settable over current protector |
AVR Range (2 Bucks,2 Boosts) | Enhanced Buck: +15% of selected nominal voltage Buck mode: +5% of selected nominal voltage Boost mode: -5% of selected nominal voltage Enhanced Boost: -12.5% of selected nominal voltage |
Phase | Single phase with ground |
3.Battery
Battery type | Sealed Lead Acid Battery |
Rated Charging Voltage | 220.8Vdc |
Typical backup time | >5min |
Charging method | Smart pulse charging with two charging modes. Quick charging when battery is not fully charged, trickle charging when battery is 90% fully charged. |
Charging current(MAX) | 1.0A(6KS,10KS:4.0/8.0A) |
Protection | Over current protection & Over charging voltage protection (SCR control) Thermal protection (CPU control) When temperature inside UPS is over 45°C,charger will stop charging for 2.5 minutes followed by an 1.5 minutes charging. The cycle will be repeated until the temperature is lower than 44°C. |
Temperature Compension | Yes |
Numbers of Battery | 20 |
4.Optional Features
ECO Mode | Support |
CVCF | Support |
PDU | Support |
Remote Panel | Wired Type,Up to 100M Length |
Parallel Redundancy | Up to 4 Units maxium(Option) Up to 4 Units maxium(Option) |
5.Environmental and Safety
Operating Temperature | 0°C to 40°C (32°F to 104°F) | |
Transit/storage Temperature | -15°C to 55°C (5°F to 131°F) | |
Relative Humidity | 20-90%(NON-CONDENSING) | |
Operating Altitude | 0 ~ 3000 meters | |
Audible noise | Less than 50 dBA | |
Safety Markings | BSMI | CE |
EMC | Class B, EN50091-2, FCC part15, IEC1000-2-2 | |
Quality control system | ISO 9001:2000 | |
Noise Level | <60dB@1 Meter |
6.Indicator
LED Version | Load Level/Battery Level/Battery;Mode/AC Mode/Bypass Mode/Fault |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously Sounding |
7.Interface
Smart RS-232 | Software supports Windows Family.Sun Solaris, IBM Aix,Compaq True64,SGIIRIX ,FreeBSD.HP-UX,and MAC |
USB (Option) | Windows Family& MAC |
Internal Slot (Option) | SNMP/AS400 Relay Card/Rs485 |
EPO(Option) | Support Emergency Shutdown |
8.Physical
Dimensions: (D×H×W) | 570*260*717mm | |
N.W/G.W(kg) | 6KVA:90 6KS:35 | 10KVA:93 10KS:38 |
Packing | PBP standard Packing,Export carton for each unit |
3.Pictures
4. Typical Application
Servers, Data centers, Critical network devices, Sensitive electronic equipment, Telecom