2kva Single Phase Outdoor UPS Ip66
USD $1 - $1,999 /Piece
Min.Order:50 Pieces
Foshan Baykee New Energy Technology Incorporated Company
2kva Single Phase Outdoor UPS Ip66
2kva outdoor ups ip66 brief description:
HW series online outdoor base station special UPS, is the global newest period control component and more advanced software perfect combine full intelligent digital product. That series product uses the six generator low-loss large power IGBT and static switch to be power component, it fully adopt digital control technique with available online programmable high speed microprocessor(MCU), and it is the perfect performance in digital electric technique.
HW series UPS capacity range from 1KVA-20KVA, with 100% suitable grid environment, widely used in communication industry,outdoor communicate station.
2kva outdoor ups ip66 main features:
1,Completely high quality with large power UPS
2,Adopt digital control technique, full intelligent digital design
3,Advanced digital electric system super stable operation
4,Battery intelligent management, durable and free from worry.
Intelligent detection system whole protection
Intelligent communicate tool remote control
5,Adopt high precision SMD technique, whole machine highly precision.
6,Basic with life period evaluate precise research, more save energy:
7,Super Clearly screen information processing technology, no restrict between user and UPS.
2kva outdoor ups ip66 Other function advantage
8,Super adapt to the reliability of the environment.
HW series with characteristic under a harsh environment, stronger waterproof, dustproof, antifreeze, heat insulation and function makes it more reliable safety.
9,The load characteristics of superior
Completely suitable from 0%-100% load jumping, and no need to changed to bypass, and protect output stable.
10,Perfect protection function
With Input and Output over loss voltage protection,input surge protection,phase protection,batteries over charging and discharging protection,output overload short circuit protection,temperature higher protection and so on.
11,The dynamic characteristics of high performance
Adopting instantaneous control mode and the effective value and so on many kinds of feedback control, realized the high dynamic adjustment, reduce output voltage distortion degree.
12,Optional input harmonic filter
Effectively restrain the input harmonic pollution and improve the power factor UPS input, reduce the input of the harmonic current.
13,Optional battery circuit module
Optional battery inspection module can be measuring on individual parameters, and in the display board to display. If the battery failure immediately alarming, to notice the administrator.
14,Personalized Settings
Personalized Settings can be based on user electricity requirement to UPS to work state setting, the user can choose UPS working patterns, ECO energy conservation work patterns, EPS work patterns.
2kva outdoor ups ip66 spec:
model (kva) | 2kva | |
Power(KW) | 1600w | |
Working pattern | power frequency double conversion pure sine wave online | |
Phase | Single(L+N+G) | |
input powe factor | 0.85 | |
Rectifier | Input Nominal Voltagle | 220V-240VAC |
Range | ±25% | |
Input Nominal Frequency | 50HZ/60Hz±10% | |
Output Wave | <2% | |
Soft start | 0-100%5sec | |
Charging | Charging Model | First constant current than constant voltage, with temperature compasation |
Float charge Voltage | 55VDC | |
Equalized Charging | 56.8VDC | |
Temperature Compensation | 3m V/°C(1pcs) | |
Charging Current | 0.1C(Basic battery capacity setting automatic adustment | |
Charging Power | 20% of Nominal capacity | |
Battery | Battery type | Maintenance-free Lead-acid Battery |
Battery Capacity | 7-999AH can be setting(Basic on different power capacity range | |
Invertor | Phase | Single Phase |
Nominal Voltage | 220VAC | |
Output Voltage Stable | ±1%(Stable Load,±5%(Load Surging) | |
Frequency Stable | 50HZ±5%(asynchronism) | |
Crest Factor | >3:1 | |
Output Wave THD | Sine Wave, Line load<1%; None Line load<3% | |
Behavioral Characteristics | Transient Voltage<5%(Jump from 0 to 100%), Transient recover time<10ms | |
Overload Protection | 115% normally working, 125% 10 min, 150% 1min, 200%1s | |
Invertor effeciency | >93%(Full Load) | |
Bypass | Phase | Single Phase (L+N) |
Nominal Voltage | 220VAC | |
Transform Time | 0ms(static switch transform) | |
Protect Function | Input protection | Input high-low voltage over resist,frequency over resist |
Output protection | Over current,short circuit,power factors too low | |
Batteries protection | Over Charging protection,Over Discharging protection | |
Temperature Protection | Environment Over temperature protection,invertor over temperature protection | |
hardware fault protection | Auxiliary power supply circuit breaker tripped, fuse, abnormal broken boot power components through a voltage protection. | |
System Parameters | Working Environment | Environment temperature -35°C-65°C,Altitude <2000meters |
Cooling Method | Low temperature to be automatic heating; Compulsory air-cooled adopts the automatic temperature at high temperature. | |
Commnuicated Method | RS232,RS485,optional dry connection port,SNMP card(Remote monitoring network. | |
Resist Surge capacity | 10/700μS, 5KV; 8/20μS, 20KA | |
Protection Level | IP21 | |
Safe Function | Input/output of resistance to report 3000 VAC, leakage current is less than 3.5 mA; Insulation resistance greater than 2 MΩ(500VDC) | |
Noising dB | 45-50 | |
Weight(KG) | 115kgs |