MODEL | WDR-240-48 | |
OUTPUT | DC VOLTAGE | 48V |
RATED CURRENT | 5A | |
CURRENT RANGE | 0 ~ 5A | |
RATED POWER | 240W | |
RIPPLE&NOISE (max.) Note.2 | 150mVp-p | |
VOLTAGE ADJ. RANGE | 48 ~ 55V | |
VOLTAGE TOLERANCE Note.3 | ±1.0% | |
LINE REGULATION | ±0.5% | |
LOAD REGULATION | ±1.0% | |
SETUP, RISE, HOLD UP TIME | 800ms,150ms/,18ms/ 400VAC 1500ms,150ms,18ms/230VAC at full load | |
INPUT | VOLTAGE RANGE | 180 ~ 550VAC 254 ~ 780VDC |
FREQUENCY RANGE | 47 ~ 63Hz | |
EFFICIENCY (Typ.) | 91% | |
AC CURRENT (Typ.) | 1A/400VAC 2A/230VAC | |
INRUSH CURRENT (Typ.) | COLD START 50A | |
LEAKAGE CURRENT | <3.5mA / 240VAC | |
PROTECTION | OVER LOAD | 105 ~ 130% rated output power |
Protection type : Constant current limiting, recovers automatically after fault condition is removed | ||
OVER VOLTAGE | 56 ~ 65V | |
Protection type : Shut down o/p voltage, re-power on to recover | ||
OVER TEMPERATURE | 90°C-5°C (TSW1) detect on heatsink of ; (12V),110 5 (24V) power transistor 100°C- 5°C (48V) (TSW1) detect on heatsink of power diode | |
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down | ||
FUNCTION | DC OK REALY CONTACT RATINGS (max.) | 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load |
ENVIRONMENT | WORKING TEMP. | -30~+70°C (Refer to derating curve) |
WORKING HUMIDITY | 20~95% RH non-condensing | |
STORAGE TEMP., HUMIDITY | -40~+85°C, 10~95%RH | |
TEMP. COEFFICIENT | ±0.03%/°C (0~50°C) | |
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, period for 72min. each along X, Y, Z axes | |
SAFETY & EMC (Note 4) | SAFETY STANDARDS | UL508 approved, IEC60950-1 CB approved by SIQ, design refer to GL |
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC | |
EMC EMISSION | Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3 | |
EMC IMMUNITY | Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A approved | |
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH | |
OTHERS | MTBF | 141.1K hrs min. MIL-HDBK-217F (25 ) |
DIMENSION | 63*125.2*113.5mm (W*H*D) | |
PACKING | 1.06Kg; 12pcs/13.7Kg/1.06CUFT | |
NOTE | 1 All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. . Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. |