UL CE approved Meanwell 48V 60W Single Output Industrial DIN Rail Power Supply
USD $1 - $10 /Piece
Min.Order:10 Pieces
Hangzhou Nuohan Electronics Co., Ltd.
Meanwell 48V 100W Single Output Industrial DIN Rail Power Supply/48v Industrial DIN Rail 100w
Meanwell single output Industrial slim din rail power supply EDR-75-24 75W 24V
Meanwell din rail DRA-60-24 60w 24v 2.5a industrial din rail power supply
Meanwell NDR-120-48 120w 2.5A 48V aluminum Industrial DIN RAIL power supply
Meanwell din rail EDR-75-48 75W 48V din rail power supply Single Ouput Industrial plastic DIN RAIL
MODEL | MDR-60-48 | |
OUTPUT | DC VOLTAGE | 48V |
RATED CURRENT | 1.25A | |
CURRENT RANGE | 0~1.25A | |
RATED POWER | 60W | |
RIPPLE & NOISE (max.) Note.2 | 200MVP-P | |
VOLTAGE ADJ. RANGE | 48 ~ 56V | |
VOLTAGE TOLERANCE Note.3 | ±1.0% | |
LINE REGULATION | ±1.0% | |
LOAD REGULATION | ±1.0% | |
SETUP.RISEHOLD.TIME Note.5 | 500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load | |
HOLD UP TIME (Typ.) | 50ms/230VAC 20ms/115VAC at full load | |
INPUT | VOLTAGE RANGE | 85 ~ 264VAC 120 ~ 370VDC |
FREQUENCY RANGE | 47~63HZ | |
EFFICIENCY (Typ.) | 87% | |
AC CURRENT (Typ.) | 1.8A/115VAC 1A/230VAC | |
INRUSH CURRENT (Typ.) | COLD START 30A/115VAC 60A/230VAC | |
LEAKAGE CURRENT | <1mA / 240VAC | |
PROTECTION | OVER LOAD | 105 ~ 150% rated output power |
Protection type : Hiccup mode, recovers automatically after fault condition is removed | ||
OVER VOLTAGE | 57.6~ 64.8V | |
Protection type : Shut down o/p voltage, re-power on to recover | ||
FUNCTION | DC OK SIGNAL | Relay contact rating(max.): 30V/1A resistive |
ENVIRONMENT | WORKING TEMP | -20~+70°C (refer to output load derating curve) |
WORKING HUMIDITY | 20~90% RH non-condensing | |
STORAGE TEMP HUMIDITY | -40~+85°C 10~95%RH | |
TEMPCOEFFICIENT | ±0.03%(0~50°C) | |
VIBRATION | Component:10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | |
SAFETY&EMC Note 4) | SAFETY STANDARDS | UL508, UL60950-1, TUV EN60950-1 approved, NEC class 2 / LPS compliant (24V,48V only) |
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | |
ISOLATIONRESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC 25°C 70%RH | |
EMI CONDUCTICN& RADIATION | Compliance to EN55011, EN55022(CISPR22)classB | |
HARMONICCURRENT | Compliance to EN61000-3-2,-3 | |
EMS IMMUNITY | Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A | |
QTHERS | MTBF | 299.2Khrs min MIL-HDBK-217F(25°C) |
DIMENSION | 40*90*100mm(L*W*H) | |
PACKING | 0.33Kg; 42pcs / 14.8Kg / 0.82CUFT | |
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time. |