Meanwell high frequency inverter/3000W True Sine Wave DC-AC Power Inverter Quality Choice
USD $1 - $10 /Piece
Min.Order:10 Pieces
Hangzhou Nuohan Electronics Co., Ltd.
Meanwell 1kw inverter/1000W True Sine Wave DC-AC Power Inverter/1000w power inverter circuit
Meanwell 1000W True sine wave DC-AC Power inverter Quality Choice Most Popular
Meanwell 200w 48v inverter True Sine Wave DC-AC Power ac inverterwith charger Quality Choice
Meanwell inverter 24v/200W True Sine Wave DC-AC Power/pure sine wave inverter with charger
Mean well TS-200-212 True Sine Wave Power transistor inverter 200W
MODEL | TS-3000-212 | |
OUTPUT | RATED POWER (Typ.) | 3000W |
MAXIMUM OUTPUT POWER(Typ.) | 3450W for 180 sec. / 4500W for 10 sec. / surge power 6000W for 30 cycles | |
AC VOLTAGE | Factory setting set at 230VAC | |
200 / 220 / 230 / 240VAC selectable by setting button S.W | ||
FREQUENCY | 50 ±0.1Hz 50/60Hz selectable by setting buttonS.W | |
WAVEFORM | True sine wave (THD<3%) at rated input voltage | |
AC REGULATION (Typ.) | ±3% | |
SAVING MODE (Typ.) | Default disabled. Load≤5W will be changed to standby mode | |
FRONT PANEL INDICATOR | Battery voltage level, output load level, saving mode, fault and operation status | |
INPUT
| BAT. VOLTAGE | 12V |
VOLTAGE RANGE (Typ.) Note. 3, 6 | 10.5 ~ 15VDC | |
DC CURRENT (Typ.) (Typ.) | 300A | |
NO LOAD DISSIPATION(Typ.) | ≤10W at standby saving mode | |
OFF MODE CURRENT DRAW(Typ.) | ≤1mA | |
EFFICIENCY (Typ.) Note.1 | 89% | |
BATTERY TYPES | Open & sealed Lead Acid | |
BATTERY INPUT PROTECTION | FUSE | 40A*12 |
BAT. LOW ALARM Note.6 | 11.3V | |
BAT. LOW SHUTDOWN Note.6 | 10.5V | |
BAT. POLARITY | By internal fuse open | |
OUTPUTPROTECTION | OVER TEMPERATURE | 80°C ± 5°C |
Protection type : Shut down o/p voltage, re-power on to recover | ||
OUTPUT SHORT | Protection type : Shut down o/p voltage, re-power on to recover | |
OVER LOAD (Typ.) | 105 ~ 115% load for 180 sec., 115% ~ 150% load for 10 sec. | |
Protection type : Shut down o/p voltage, re-power on to recover | ||
CIRCUIT BREAKER | AC output receptacle:15A | |
GFCI PROCTECTION | None | |
ENVIRONMENT | WORKING TEMP. Note.2 | 0~+40°C at 100% load 60°C at 50% load |
WORKING HUMIDITY | 20%~90% RH non-condensing | |
STORAGE TEMP., HUMIDITY | -30~+70°C / -22~ +158 F, 10~95%RH | |
VIBRATION | 10 ~ 500Hz, 3G 10min./1cycle, 60min. each along X, Y, Z axes | |
SAFETY&EMC | SAFETY STANDARDS | None |
LVD | EN60950-1 | |
WITHSTAND VOLTAGE | Bat I/P - AC O/P:3.0KVAC AC O/P - FG:1.5KVAC | |
ISOLATION RESISTANCE | Bat I/P - AC O/P, Bat I/P - FG,AC O/P-FG:100M Ohms / 500VDC / 25°C/ 70% RH | |
| EMC EMISSION | Compliance to EN55022 class A, 72/ 245/ CEE, 95/ 54/ CE, E-Mark |
EMC IMMUNITY | Compliance to EN61000-4-2,3,4,5,6,8,11 | |
OTHERS | CONTROL WIRING | RJ11 -RS232 (Option) |
DIMENSION | 466.8*283.5*100mm (L*W*H) | |
PACKING | 12.9Kg; 1pcs/14Kg/1.98CUFT | |
NOTE | 1. Efficiency is tested by 2100W, linear load at 13V, 26V, 52V input voltage. 2. Output derating capacity referenced by curve 1. 3. Input derating capacity referenced by curve 2. 4. DC current is tested by 3000W, linear load at 12V, 24V, 48V input voltage. 5. All parameters not specified above are measured at rated load, 25°C of ambient temperature. 6. The tolerance of each voltage value by models is:112/212 →±0.5V;124/224 →±1V;148/248 →±2V |
hing power supply dual output switching power supply switching power supply 12v -12v