xlpe insulated pvc sheath power cable STA steel tape armoured
USD $1 - $25 /Kilometer
Min.Order:1 Kilometer
Zhengzhou Hongda Cable Co., Ltd.
xlpe insulated pvc sheath power cable STA steel tape armoured
APPLICATION
The cables are mainly used in power stations, mass transit underground passenger systems,
airports, petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS
Basic design adapted to IEC 60502-1
FIRE PERFORMANCE
Flame Retardance (Single Vertical | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE |
Reduced Fire Propagation | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.
VOLTAGE RATING
600/1000V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, normal stranded or compact stranded
Insulation: Extruded cross-linked XLPE compound.
Filler, binder and inner covering: PP, PET, PVC
Armouring: Double steel tape
Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance,
anti rodent and anti termite properties can be offered as option. Compliance to fire performance
standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the
PVC compound and the overall cable design. LSPVC can also be provided upon request.
COLOUR CODE
Insulation Colour as per BS7671
| With Earth Conductor | Without Earth Conductor |
2Cores | - | Brown, Blue |
3Cores | Yellow/Green, Brown, Blue | Brown, Gray, Black |
4Cores | Yellow/Green, Brown, Gray, Black | Brown, Gray, Black, Blue |
5Cores | Yellow/Green, Brown, Gray, Black, Blue | Brown, Gray, Black, Blue, Black |
Above 5 Cores | Yellow/Green, Black Numbered | Black Numbered |
Sheath Colour: Black (other colors upon request)
Physical AND THERMAL PROPERTIES
Temperature range during operation: Max.90°C for XLPE
250°C in short-circuit for 5secs max.
Minimum bending radius: 10x Overall Diameter
Voltage Drop (Per Amp Per Meter)
Conductor cross-sectional area | 2-core cable d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, 3-phase a.c. | 2 cables, single- phase a.c. | 3 or 4 cables, | ||||
3-phase a.c. | |||||||||
In ducts or in ground | In ducts or | ||||||||
in ground | |||||||||
1 | 2 | 3 | 4 | 5 | 6 | ||||
mm2 | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | ||||
6 | 7.9 | 7.9 | 6.8 | 7.9 | 6.5 | ||||
10 | 4.7 | 4.7 | 4 | 4.7 | 3.9 | ||||
16 | 2.9 | 2.9 | 2.5 | 2.9 | 2.6 | ||||
r | x | z | r | x | z | ||||
25 | 1.85 | 1.35 | 0.16 | 1.9 | 1.6 | 0.14 | 1.65 | 1.9 | 1.6 |
35 | 1.35 | 1.35 | 0.155 | 1.35 | 1.15 | 0.135 | 1.15 | 1.35 | 1.2 |
50 | 0.98 | 0.99 | 0.155 | 1 | 0.86 | 0.135 | 0.87 | 1 | 0.87 |
70 | 0.67 | 0.67 | 0.15 | 0.69 | 0.59 | 0.13 | 0.6 | 0.69 | 0.61 |
95 | 0.49 | 0.5 | 0.15 | 0.52 | 0.43 | 0.13 | 0.45 | 0.52 | 0.45 |
120 | 0.39 | 0.4 | 0.145 | 0.42 | 0.34 | 0.13 | 0.37 | 0.42 | 0.36 |
150 | 0.31 | 0.32 | 0.145 | 0.35 | 0.28 | 0.125 | 0.3 | 0.35 | 0.3 |
185 | 0.25 | 0.26 | 0.145 | 0.29 | 0.22 | 0.125 | 0.26 | 0.29 | 0.25 |
240 | 0.195 | 0.2 | 0.14 | 0.24 | 0.175 | 0.125 | 0.21 | 0.24 | 0.21 |
300 | 0.155 | 0.16 | 0.14 | 0.21 | 0.14 | 0.12 | 0.185 | 0.21 | 0.19 |
400 | 0.12 | 0.13 | 0.14 | 0.19 | 0.115 | 0.12 | 0.165 | 0.19 | 0.18 |