192VDC 6KVA 10KVA UPS - NEW
USD $80 - $200 /Set
Min.Order:10 Sets
Shenzhen Santek Power Co., Limited
Castle C6K(S)~3C20KS is a powerful product range with high adaptability and flexibility. Its cut-edge digital control technology of DSP (Digital Signal Processor), can greatly improve the product performance and system reliability, and deliver a compact integration with higher power density. Meanwhile, Castle C6K(S)~3C20KS is especially tailored for all customer's personalized demands to provide powerful scalable functions.
Tailored for Grid Environment
Output power factor up to 0.8
Flexible Configuration on Demand
Compact Design, Lower NoiseIntelligent battery management
High Reliability
Rich Communication and Monitoring Features
Specification | ||||||
Dream castle online 6K-10K | ||||||
MODEL | 6KN/6KS | 10KN/10KS | ||||
Rated Power | 6KVA/4.8KW | 10KVA/8KW | ||||
Input | ||||||
Nominal Input AC Voltage | 220VAC | |||||
Phase | Phase + Neutral + Ground | |||||
Turn On Voltage Range | 120 ~ 275.0 VAC | |||||
Bypass Voltage Range | 187~ 264.0 VAC | |||||
Bypass Low Comeback | at least 10 seconds delay | |||||
Input Power Factor | > 0.99 (Full R/RCD load) | |||||
Input THDi | < 10%,with R full load At Line normal(THD-V<1%) | |||||
Generator size | 2.2 time of UPS rating power | |||||
Nominal Frequency | 50.0 / 60.0Hz | |||||
Current (RMS) | 25-43 A | |||||
Current protection | 80A Fuse(Line mode) & 32A Breaker(Internal automatic bypass) | |||||
OUTPUT | ||||||
Output Power Factor | 0.8 | |||||
Waveform | Sine wave | |||||
Wiring | 1 phase + N | |||||
Nominal Voltage | 220VAC | |||||
Output Current | 27.27A-43A | |||||
Voltage Regulation | ±1% | |||||
Transient Recovery | 60 ms recover to 90%~110% nominal voltage | |||||
Load Crest Ratio | >3:1 | |||||
Output Frequency Range | ||||||
Line Mode | (46~54)Hz / (56~64)Hz | |||||
Battery Mode | (50±0.05 )Hz / (60±0.05)Hz | |||||
Overload Capability | ||||||
Line/Battery Mode | 1 minutes minimum, then transfer to bypass and alarm | 105%<Load≤125% Bypass over load > 30 minutes then turn off output; | ||||
30 seconds minimum, then transfer to bypass and alarm | 125%<Load≤150% Bypass over load > 1 minutes then turn off output; | |||||
0.5 seconds minimum then transfer to bypass and alarm | Load>150% Depend on Breaker capability; | |||||
TRANSFER TIME | ||||||
Line-Battery Mode | 0ms | |||||
Line-Bypass Mode | <4 ms | |||||
BATTERY & CHARGER | ||||||
Rated Charge Voltage | 216V | |||||
Charging Power | 220W+/-5% ,1000W+/-5% | |||||
Charging Current | 4.2 A | |||||
Backup Time | >4 min(Depend on the capacity of external battery, at RCD Full load) | |||||
ENVIRONMENT | ||||||
Working Temperature | 0°C~40°C | |||||
Altitude | <1000m | |||||
Humidity | 20%~90% | |||||
Storage Temperature | -25°C~55°C | |||||
Acoustic Noise | <55dB | |||||
Outline Dimension | ||||||
Total W×D×H(mm) | 380*680*834 | 390*595*578 | 380*680*834 | 390*595*578 | ||
Gross Weight(kg) | 66 | 23 | 67 | 24 | ||
Communication | ||||||
RS232 | Winpower 2003 | |||||
Intelligent Slot | Yes | |||||
EPO | adapt to NEC 645-11 | |||||
Note: Can add “SNMP Card/CMC Card/USB Card/ETD Card/ AS400 Card” | ||||||