INDUSTRY UPS(parallel/redundant): G-HM,G-HT 8000VA-200000VA |
| | | | | | | | | | | | | | | |
Model No. | HM8 | HM10 | HM15 | HM20 | HM30 | HT10 | HT20 | HT30 | HT40 | HT60 | HT80 | H100 | H120 | H160 | H200 |
Power Capacity(VA) | 8K | 10K | 15K | 20K | 30K | 10K | 20K | 30K | 40K | 60K | 80K | 100K | 120K | 160K | 200K |
Power Capacity(W) | 6.4K | 8K | 12K | 16K | 24K | 8K | 16K | 24K | 32K | 48K | 64K | 80K | 96K | 128K | 160K |
Input |
Nominal Voltage | 380VAC or 190VAC (3 phases 4 wires and ground) |
Voltage Range | 304-456VAC |
Frequnency Range | 50Hz or 60Hz ±5% |
Power Factor | over 0.97 |
Phase | 3 Phases + GND |
Max I/P current | 15A | 18A | 27A | 36A | 54A | 18A | 37A | 55A | 72A | 108A | 130A | 160A | 190A | 245A | 310A |
Output |
Voltage | 120VAC/230VAC±1% | 380VAC/400VAC/415VAC±1% or 192VAC±1% |
Frequnency | Sync to input(line mode),50Hz or 60Hz±0.05 |
Waveform Type | pure sinewave |
Phase | 3 Phases 4 wires + GND |
Voltage Distortion | ≤3% for linear load |
Overload Capacity | 110% for 300mins or 125% for 10mins or 150% for 1min then transfer to bypass & alarm |
Power Factor | 0.8 |
Crest Power | 3 times of ratings |
Batteries |
type | Maintenance-free sealed Lead-Acid battery |
Nominal DC Voltage | 384VDC | 432VDC | 480VDC |
Charging Time | 8-10 hours for 90% capacity after full discharge |
Transfer time | 0 ms(line to battery mode) |
Protections | overload,short circuit,over temperature,surge,line abnormal |
Display |
LED | Operation mode(online,battery,bypass),battery capacity,abnomal,overload |
LCD | I/P voltage & frequency,battery volt,O/P voltage & frequency, |
load percentage,Operation mode,temperature inside |
Efficiency | over 0.85 for whole unit |
Comunications & Management |
Interface Port | RS-232 |
Intelligent Slot | Dry Contact/EPO/SNMP Card (optional) |
Bypass | Static state + manual maintenance bypass |
Enviromental |
Operation Enviroment | 0-40°C |
Storage Enviroment | -25°C~55°C |
Relative Humidity | 0-95%RH(non-condensing) |
Audible Noise | less 55dB | less 60dB | less 65dB | less 70dB |
Altitude | Nominal power output for less 1000m, reduce output 1% for increase of 100m,Max 4km |
Physical |
Net Weight(KG) | 190 | 200 | 220 | 240 | 269 | 223 | 260 | 336 | 351 | 497 | 556 | 756 | 901 | 1300 | 1350 |
Gross Weight(KG) | 247 | 256 | 265 | 288 | 305 | 280 | 317 | 393 | 408 | 574 | 633 | 856 | 1001 | 1400 | 1450 |
Dimension,DxWxH(mm) for "S" type | 555 X 725 X 1220 | 800X745X1400 | 1070X745X1400 | 1420X745X1810 |
Optional Components | Isolation transformer,Parallel modules,Harmonic wave filter,SNMP adapter,Monitoring software |
Safety Standard | EN50091-1 EN50091-2 CLASS A, IP20 |
*Specifications are subject to change without prior notice. |