Product Details

M110E Remote IO Module with 4DI+4DO+1RS485 for Controlling Digital Consumer Devices

Brand Name BLIIOT
Place of Origin China
Model Number M110E

Product Features

The M Series Modbus Remote I/O Module is an industrial class, isolated designed, high reliability, high stability and high precision data acquisition module, embedded 32-Bit High Performance Microprocessor MCU, provides a RS485 interface.  It provides multi I/O, supports standard Modbus RTU, can be intergraded into SCADA, OPC server, HMI and other automation systems. It is design for working in the harsh industrial application environment, widely used in a variety of industrial automation, security monitoring system, automatically measurement and control system.

The M Series Modbus Remote I/O module provides different I/O ports for variety applications. Includes optical-isolated digital inputs, compatibles dry contact and wet contact, supports max 10MHz high speed pulse counter, the DIN1 can be used for encode, digital outputs supports 10Hz~300Khz high speed pulse output or relay outputs, the DO1 supports PWM high-speed pulse output, the output duty cycle from 10-90%; DO2 can be used to control the direction of the stepper motor, isolated 12bits analog inputs, supports 0~5V, 0~10V, 4~20mA, 0~20mA analog signal, 12bits analog outputs, supports 0~10VDC signal output, resistance thermal detector inputs compatibles 2/3 wires PT100 and PT1000. All of the I/O ports are high sampling frequency and special filtering strategy to ensure its reliability.

The M Series Modbus Remote I/O module can work at wide working voltage range, the range is 12 ~ 36VDC with anti-reverse protection design. Also, it provides 1channel 12~36VDC power output for external device to save wiring cost.


M Series Modbus Remote I/O Module Table

Model

Descriptions

DC Output

DC Input

Classic Power Consumption

M100

1 RS485, 2 DI, 2 AI, 2 DO(Sink) or Relay

1 DC

12~36VDC

0.84W-1.32W

M110

1 RS485, 4 DI, 4 DO(Sink) or Relay

1 DC

M120

1 RS485, 4 DI, 4 AI, 2AO, 4 DO(Sink) or Relay

1 DC

0.84W-1.32W

M130

1 RS485, 8 DI, 4 DO(Sink) or Relay

1 DC

12~36VDC

0.64W-1.84W

M140

1 RS485, 8 DI, 8 DO(Sink) or Relay

1 DC

M150

1 RS485, 8 DI, 4 AI, 4 DO(Sink) or Relay

1 DC

M160

1 RS485, 8 DI, 8 AI, 8 DO(Sink) or Relay

1 DC

M200

1 RS485, 2AO

1 DC

12~36VDC

0.84W-1.32W

M210

1 RS485, 4 DI

1 DC

0.84W-1.32W

M220

1 RS485, 4 DO(Sink) or Relay

1 DC

M230

1 RS485, 4 AI

1 DC

M240

1 RS485, 4 RTD, 2/3 wire PT100/pt1000

---

0.6W-0.84W

M310

1 RS485, 8 DI

1 DC

12~36VDC

0.64W-1.84W

M320

1 RS485, 8 DO(Sink) or Relay

1 DC

M330

1 RS485, 8 AI

1 DC

M340

1 RS485, 8 RTD, 2/3 wire PT100/pt1000

12~36VDC

0.6W-0.84W

M410

1 RS485, 16 DI

1 DC

0.74W-0.96W

M420

1 RS485, 16 DO(Sink) or Relay

0.6W-0.85W



 Mainly Features

Ø Embedded 32-Bit High Performance Microprocessor MCU, inbuilt watchdog;

Ø Power supply 12~36VDC with over voltage and phase-reversal protection;

Ø Optical isolated digital input(Compatible Dry or Wet type);

Ø DIN1 supports max 10MHz high speed pulse counter, can be used to encode measurement;

Ø Digital output(Sink) or relay output, supports 10Hz~300KHz high speed pulse output;

Ø DO1 supports PWM high-speed pulse output, the output duty cycle from 10-90%;

Ø DO2 can be used to control the direction of the stepper motor;

Ø Isolated analog input, 12-bit resolution, supports 0~20mA,4~20mA,0-5VDC, 0-10VDC;

Ø Analog output, 12-bit resolution, supports 0-10VDC;

Ø RTD input, supports PT100 and PT1000 resistance sensor, compatible 2 or 3 wires;

Ø High sampling frequency and special filtering strategy to ensure reliability;

Ø 1 RS485 Serial port, supports Modbus RTU slave;

Ø Provides 1 channel VDC power source output for external device, saving wiring cost;

Ø LED instructions work status, with reset button to reset, easy on-site installation and commissioning;

Ø Using metal shell, protection class IP30. Metal shell and system security isolation, especially suitable for industrial applications in the field;

Ø Small size, L105 * W88 * H30mm, compatible wall installation and DIN35mm industrial rail installation.

4. Technical Specifications

• Digital Input

Sensor Type

Wet Contact (NPN or PNP), Dry Contact

I/O Mode

DI or Event Counter

Dry Contact

• On: short to GND, logic=1
• Off: open, logic=0

Wet Contact (DI to COM)

• On: 10 to 30 VDC,logic=1
• Off: 0 to 3 VDC,logic=0

Counter Frequency

Only the 1st Channel can be used as pulse counter, Compatibles DI and counter simultaneously. Counter value will save after power off.

High Speed Mode: Max. 10Mhz(Default);

Low Speed Mode: Max. 10KHz (Optional, can open the cover to choose low speed mode.)

Digital sampling frequency

500Hz

Digital filtering strategy

Continues 3 times

Isolation

Optical Isolated,3k VDC or 2k Vrms

• Digital Output

Type

Sink or Relay(DC 5A/30V,5A/250VAC)

I/O Mode

DO or Relay or Pulse Output

Pulse Output Frequency

10Hz~300KHz(Only the 1st Channel is Sink type can be used as high speed pulse output, DO1 supports PWM high-speed pulse output, the output duty cycle from 10-90%; DO2 can be used to control the direction of the stepper motor.)

Over-Voltage Protection

50 VDC

Over-Temperature Shutdown

175°C (typical), 150°C (min.)

Load Current

Max.500 mA per channel

Digital sampling frequency

500Hz

Isolation

If DO is Sink type, then no isolation. If it is Relay, then is electrical isolation.

• Analog Input

Type

Differential input

Resolution

12 bits

I/O Mode

Voltage / Current (backside switch selectable)

Input Range

0~5VDC , 0~10VDC, 0~20 mA, 4~20mA,

Accuracy

±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C

Sampling frequency

20Hz

Isolation

Electrical isolation

• RTD Input

Sensor Type

PT100 or PT1000

Measurement Range

-120~+420

Resolution

0.1°C or 0.1 ohm

Input Connection

2- or 3-wire

Accuracy

±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C

Sampling frequency

20Hz

Isolation

No

• Analog Output

Type

Differential input

Resolution

12 bits

Output Range

0 to 10 VDC

Drive Current

1A (max.)

Accuracy

±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C

Isolation

No

• Working Power Requirements

Input Voltage

12~36VDC for no-AO output model,

24`36VDC for AO output model;

Peak Voltage:+40VDC, Power consumption: Less than 1.7W,

If equipped relay output, then each Relay action: 0.15W.

Input Current

139 mA @ 24 VDC

• Power Output

Output Voltage

12~36VDC, equal to the input voltage.

Output Current

139 mA @ 24 VDC

• Serial Port

RS485

MODBUS RTU Slave.

Protection

15KV ESD Protection

Modbus Slave address

1~247

Response Time

10mS

Baud Rate

1200,2400,4800,9600,19200,38400,57600,115200Bps;

• Physical Characteristics

Wiring

I/O cable max. 14 AWG

Dimensions

105 x 88 x 30 mm

Weight

Under 205 g

Mounting

DIN rail or wall

• Environmental Limits

Operating Temperature

Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Ambient Relative Humidity

5 to 95% (non-condensing)

Altitude

Up to 3000 m


Special instructions for ordering

1) If the model provides digital input, the DIN default type: wet contact, optional: dry contact. The input type cannot be changed after manufacturer delivered. The DIN1 default is high-speed count mode; it can be changed to low-speed count mode by open the shell and change the internal jumper. If require dry contact input, please note when ordering, if DIN1 require high-speed pulse count mode then must be wet contact.

2) If the model provides digital output, the DO default type: SINK, optional: Relay. The output type cannot be changed after manufacturer delivered. The DO1 supports PWM high-speed pulse output, the output duty cycle from 10-90%; DO2 can be used to control the direction of the stepper motor. If require relay output, please note when ordering, if DO1, DO2 used for high-speed pulse output then must be Sink.

3) The model number: M240, M340 support thermal resistance temperature transmitter default type: PT100, optional: PT1000, if you need PT1000 type of thermal resistance, please note when ordering.

4) The valid number of I / O ports corresponding to the model number is described in the Model List, the not included I/O port in the model is invalid, although in the hardware reserved them.


You May Like

Find Similar Products By Category

You May Like

View More
Chat Now Contact Now