ACREL ASJ Series of action relay of after-current, low-voltage circuit break or low-voltage contactor can be made up for combined after-current production device, which is mainly applied for the TT and TN system distributing circuit with the alternating current 50Hz, the rated voltage 400V or below.
ASJ Series of action relay of after-current is applied in the earth fault protection for the electric circuit, so as to prevent the equipment damage and the fire accident of electric equipment caused by the ground fault current, moreover, it also can provide indirect contact protection against the electric shock risk.
Technical Parameter | Indicator |
AC type | A type |
Power supply | Voltage range | AC110V、AC220V (±10%) | AC/DC85~265V |
Power dissipation | ≤5W |
Input | Rated residual operating current I△n | 0.03、0.1、0.3、0.5(A) | 0.03、0.05、0.1、0.3、0.5、1、3、 5、10、30(A)note 3 |
Limit non-driving time △t | 0.1、0.5(s) | 0、0.06、0.1、0.2、0.3、0.5、0.8、 1、4、10(s)note |
Rated residual non-operating current I△no | 50%I△n | 50%I△n |
Performance characteristics | Sinusoidal AC | Sinusoidal AC and pulsating DC |
Frequency | 50Hz±5Hz | 50Hz±5Hz |
Operating range | -20% ~ -10%I△n | -20% ~ -10%I△n |
Output | Output mode | One is normally open and another is for transformation | One is normally closed or open, and another is for transformation |
Contact capacity | 5A 250VAC 5A 30VDC | AL1:8A 250VAC; 5A 30VDC AL2:6A 250VAC; 5A 30VDC |
Reset mode | Local reset or remote reset | Local reset, remote reset or automatic reset |
Installation and use environment | Temperature | Run temperature:-20℃ ~ +55℃,Storage temperature:-30℃ ~ +70℃ |
Humidity | ≤95%RH,no condensation, and no corrosive gas places |
Elevation | ≤2000m |
Class of pollution | Grade three |
Installation category | Type Ⅲ |
Note 3: ASJ10L-LD1A rated residual operating current IΔn is 10mA~30A continuously adjustable; Note 4: ASJ10L-LD1A limit non-driving time Δt is 0~10S continuously adjustable.
| |
| AC type residual current
Over current alarm Rated residual operated current can be set Limited non-driving time can be set 2 relays output(1 NC contact, 1 normal changeover contact) With local/remote "test" and "reset" functions |
| A type residual current measurement
Current percentage light bar indication(30%, 50%, 70%, TRIP) Rated residual operated current can be set Limited non-driving time can be set 2 relays output(1 NO contact, 1 normal changeover contact) With local/remote/automatic "test" and "reset" functions |
| AC type residual current Over current alarm
Rated residual operated current can be set Limited non-driving time can be set 2 relays output(1 NC contact, 1 normal changeover contact) With local/remote "test" and "reset" functions |
| A type residual current measurement Current percentage light bar indication(30%, 50%, 70%, TRIP) Rated residual operated current can be set Limited non-driving time can be set 2 relays output(1 NO contact, 1 normal changeover contact) With local/remote/automatic "test" and "reset" functions |