Check the insulation of the motor and motor cable as follows: 1. Check if the motor cable is connected to the motor and disconnected from the drive output terminals U2, V2, and W2. 2. Use a measurement voltage of 500 VDC to measure the insulation resistance of the motor cable and motor between each phase and the protective grounding. The insulation resistance of ABB motors must exceed 10 Mohm (reference value is 25 ° C). Please refer to the manufacturer's instructions for the insulation resistance of other motors.