3500/50 133442-01 I/O module with internal terminals
Negotiable /Piece
Min.Order:1 Piece
3500/50 133442-01
3500/50 133442-01
3500/50 133442-01
Based on the drawn gap voltage curve, determine the linear range of the sensor system, which should not be less than 2mm. The sensitivity of the sensor system should be calculated to be 7.874V/mm, and the nonlinear deviation within the linear range should not exceed 20um. The sensitivity is determined by dividing the voltage increment by the gap increment. The linear center of the sensor is the static set point of the axis displacement sensor.