Acrel RS485 Interface Modbus-RTU protocol LCD Display solar dc energy meter for home
Negotiable
Min.Order:1
Type | Function | Optional |
PZ72L-DE | ● Measurement: 1-circuit DC kWh, kVarh, U, I, P and etc ● Accuracy: 0.5% ● Rated Voltage: 1000V DC ● Rated Current: 10A DC (direct connect); 0/4~20mA DC (via Hall Sensor); 75mV (via Shunts) ● Power Supply: 85~265V AC/DC; 20~60V DC ● Standard&Certificate: CE Certificates ●Local display ●Measure voltage, current, power, forward and reverse power in DC system ●Set parameters ●Applications:DC panels, solar power, telecommunications base stations, and charging posts | ● DI/DO Function: 2/4-channel DI&2-channel DO ● ±12V Power Ouput: Paired with Hall Sensor ● Multi-rate/tariff:4 Tariff Rates and etc ●Relay alarm output |
Function | Description&Value |
Measurement | 1-circuits DC Voltage, Current, Power, kWh |
Display | LCD display |
Communication (Optional) | RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity) Baud Rate 1200~38400 bps etc. |
DI/DO Switching (Optional) | DI (Digital input): 2-channel digital input,dry contact, built-in power supply DO (Digital output): 2-channel digital output (relay output) with NO Contact, Capacity: 2A/30V DC or 2A/250V AC |
±12V Power Output (Optional) | Serve as the power supply for 1 Hall Sensors with ±12V DC |
Multi-rate/tariff (Optional) | 2 Time Schedules; 4 Time Zone for a year; 12 time periods by days set for 1 time schedule; 4 Tariff Rates (Spike, Peak, Flat, Valley); Min. Time Interval=15 min. |
Parameter | Description&Value | ||
Input | Rated Voltage | DC Voltage Input: 0~1000V DC (via direct connetion); Input Resistance: ≥ 6kΩ/V | |
Rated Current | DC Current Input: 10A DC (via direct Connection); 0~20mA or 4~20mA (via Hall Sensors); 75mV (via Shunts) | ||
Overload | Current&Voltage input overload:1.2 times rated value(continuous); 10 times rated value /1 second | ||
Power Consumption | Power consumption of each current input circuit is less than 1mW | ||
Measuring Accuracy | Class | 0.5% | |
Power Supply | Voltage Range | 85-265V AC/DC; 20~60V DC (±20%) | |
Power Consumption | ≤ 2W | ||
Pulse Constant | Voltage and current specifications:750V、300A,Default pulse constant:100imp/kWh | ||
Voltage and current specifications:1000V、300A,Default pulse constant:100imp/kWh | |||
Insulation resistance | ≥ 100MΩ | ||
Power frequency withstand voltage | Between Power supply//Switching Output// Current Input//voltage Input and Transmitting// Communication //Pulse Output//switching input AC 2 kV 1min; Between Power supply、switching output、Current Input、voltage Input AC 2 kV 1min; Between Transmitting、Communication、Pulse Output、switching input AC 1kV 1 min; |
Condition | Description&Value |
Temperature | Operation: -25℃~+65℃; Storage: -40°C ~+80°C |
Humidity | ≤95%RH,no condensation,without corrosive gas |
Altitude | ≤ 2500m |