An open circuit and short circuit on the CS31 bus are
detected by the NCB. In this case, the different CS31 bus
segments below the default are out of order. The CS31
bus segment above the default runs properly.
The leds ERRORS "OUT" or "IN" are "ON" according on
the CS31 bus in default.
This error is displayed on the central unit (FK3) as a
remote unit error.
The access to the default is different according on the type
of central unit :
07KR31 / 07KT31
– access to the default with the function block COPY to the
memory address SEG : 0h and OFFSET : 8660h
If the value is 2Ah, then almost one of the NCB's is on
default. (The red led on central unit is OFF).
The default is reset on the central unit when 0 is written
at the address 0:8660h (with the function block COPY).
– access to the default as an FK3 error number 17d with
the versions produced after April 96 (07KR31 index J
and 07KT31 index B).
07KR91 / 07KT92 / 07KT93
– access to default with the function block COPY to the
memory address SEG : C000h and OFFSET:0100h
If the value is 2Ah, then almost one of the NCB's is on
default. (The red led on central unit is ON).
The default is reset on the central unit when 0 is written
at the address 0C00/0100h (with the function block
COPY).
07CS61 (for T200)
– Version index c R202
The default is seen as a bus error without any remote unit
number.
– Version index d R202 and next
The default is set in the bit 4 of the word MW4104,03 for
the first CS31 line, MW4105,11 for the second CS31 line,
MW4107,03 for the third CS31 line and MW4108,11 of the
fourth CS31 line.
07CS91 (for T300) and UCZA/UCZB
The diagnosis is not available.