Variable Freqency Drive (VFD) Cable, XLPE Insulated, Armoured Or Non-Armoured,0.6/1kV And 1.8/3kV
Negotiable /Piece
Min.Order:1 Piece
Jiangsu Shangshang Cable Group Co., Ltd
CONSTRUCTION
Conductor: bare copper or tinned copper, class 1 (≤6mm2), or class 2, or class 5, as per IEC60228
Insulation: XLPE
Screen: copper tape(CTS), or
copper wire + copper tape(CWS+CTS), or
bare/tinned copper wire braided (BCWB/TCWB), or
Aluminium-Foil + TCWB, or
Copper tape + copper wire braided (CTS + CWB)
Inner covering(optional): lapped binder tape or extruded Polyvinyl Chloride (PVC)
Armour(optional): galvanized steel tape(DSTA), or galvanized round steel wire(SWA)
Outer sheath: Polyvinyl Chloride (PVC)
Note: extruded inner sheath and armour layer is not applicable for non-armoured cable
BPYJVP2 | VFD CABLE, CU/XLPE/CTS/PVC |
BPYJVP2R | VFD CABLE, FLEXIBLE, CU/XLPE/CTS/PVC |
BPYJVP | VFD CABLE, CU/XLPE/CWB/PVC |
BPYJVPR | VFD CABLE, FLEXIBLE, CU/XLPE/CWB/PVC |
BPYJVP3PR | VFD CABLE, FLEXIBLE, CU/XLPE/AL-FOIL+CWB/PVC |
BPYJVP12 | VFD CABLE, CU/XLPE/CWS+CTS/PVC |
BPYJVP12R | VFD CABLE, FLEXIBLE, CU/XLPE/CWS+CTS/PVC |
BPYJVP2-22 | VFD CABLE, CU/XLPE/CTS/PVC/DSTA/PVC |
BPYJVP2R-22 | VFD CABLE, FLEXIBLE, CU/XLPE/CTS/PVC/DSTA/PVC |
BPYJVP12-22 | VFD CABLE, CU/XLPE/CWS+CTS/PVC/DSTA/PVC |
BPYJVP12R-22 | VFD CABLE, FLEXIBLE, CU/XLPE/CWS+CTS/PVC/DSTA/PVC |
BPYJVP2-32 | VFD CABLE, CU/XLPE/CTS/PVC/SWA/PVC |
BPYJVP2R-32 | VFD CABLE, FLEXIBLE, CU/XLPE/CTS/PVC/SWA/PVC |
USAGE CHARACTERISTIC:
Rated voltage:Uo/U(Um) = 0.6/1kV(1.2kV), 1.8/3kV(3.6kV)
Maximum continuous operating temperature of conductor:90℃
Maximum short-circuit temperature (Max. duration 5Sec.): 250℃
Minimum ambient temperature for installation:0℃
Minimum bending radius when installation: 15 D ( D is the overall diameter of cable)
SPECIAL FEATURES ON REQUEST:
Flame retardant to IEC60332-3(Cat. A, B, C)
Fire resistant to IEC60331
Low smoke zero halogen(LSZH) to IEC61034, IEC60754
Anti-termite/anti- rodent
Use in low ambient temperature
UV resistant