Silicone Rubber Insulated Control Cable 450/750V
Negotiable /Piece
Min.Order:1 Piece
Jiangsu Shangshang Cable Group Co., Ltd
Heavy-Duty Rubber Sheathed Flexible Cable For General Purpose 450/750V
UL 1015 PVC Insulated Appliance Wire 600V (File No. E363159)
Thermoplastic Elastomer Or HEPR Insulated DC Charging Cable For Electric Vehicles 1000V
PVC Insulated And Sheathed Cable For Electric Vehicle Conductive Charging System AC Or DC 1500V
APPLICATION:
This cable is used for connection wiring of fixed or mobile electrical appliances and instruments in power distribution devices with rated voltage up to and including 450/750V, and widely used in steelworks, metallurgy, power and petrochemical industry, etc. This cable has excellent properties of high or low temperature resistant and anti-aging. These cables with silicone rubber insulation and sheath construction will not release toxic and corrosive gases are produced when burning.
STANDARD:
Q/320481SS104-2019, or other standards required by customer.
CONSTRUCTION:
Conductor: copper wire, class 1 or class 2 or class 5 as per IEC60228.
Insulation: silicone rubber (SR)
Metallic screen(optional): bare copper wire braided(BCWB), or tinned copper wire braided(TCWB), or copper tape screen(CTS)
Outer sheath: silicone rubber (SR)
TYPICAL CABLE TYPE:
Type | Description |
KGG | CU/SR/SR control cable |
KGGP | CU/SR/BCWB(TCWB)/SR control cable |
KYGGP2 | CU/SR/CTS/SR control cable |
KGGR | CU/SR/SR flexible control cable |
KGGPR | CU/SR/BCWB(TCWB)/SR flexible control cable |
KGGP2R | CU/SR/CTS/SR flexible control cable |
NUMBER OF CORES AND SIZE:
Conductor size(mm2) | Number of cores |
0.75 | 2 - 61 |
1.0 | 2 - 61 |
1.5 | 2 - 61 |
2.5 | 2 - 61 |
4 | 2 - 14 |
6 | 2 - 14 |
10 | 2 - 14 |
Core Identification And Sheath Color:
Core identification: red, with printing numbers
Sheath color: red
Note: other core identification and sheath color can be discussed as per customer’ requirement.
USAGE CHARACTERISTIC:
Continuous operating temperature: 180℃
Maximum short circuit temperature (5 Sec): 350℃
Operating ambient temperature scope: - 60℃ ~ 180℃
Minimum ambient temperature for laying: - 20℃
Minimum bending radius:≥6D for cables non-metallic screen or with copper wire braided screen ;
≥15D for cable with copper tape screen or armoured layer
Special Features on Request:
Flame retardant
Fire resistant
Low ambient temperature use
UV resistant