Industrial IOT device bidirectional electric panel modbus energy meter for energy management system
Negotiable
Min.Order:1
KPM10 three phase multifuction power | ||||||||||||
product type | measurement | special function | communication | extensions function | hole size | |||||||
KPM10 | 3 phase voltage, current, power, power factor, 4 quadrant power, frequency, etc. | Four quadrant power measurement,duplication of fees statistics;three-phrase unbalance rate current K coefficient 2-21 harmonics measurement | RS485/standard | 2DO(-R) | 2DI(-K) | 68*68mm | ||||||
Optional | optional |
KPM10 Modbus 3 phase current voltage frequency meter | ||||
Working Power Source | Operating Voltage | AC85~265V/DC80~300V | ||
Rated Power | <3VA | |||
Input Voltage | Rated Voltage | 57.7/100V,220/380V, 380/660A (needs customization) | ||
Sill Value | 5V | |||
Overload Capacity | 1.2 times rated voltage allowed,continuous work; 2 times the rated voltage allowed 1 second | |||
Power Consumption | <0.5VA/phase(rated) | |||
Measurement Range | 5~260VAC, | |||
Frequency Range | 45~65Hz | |||
Input Current | Rated Current | Default 5A,Input range 1-6A;Optional 1A,Input range 1-1.2A | ||
Sill Value | 5A Configuration,5mA;1A Configuration,0.8mA | |||
Overload Capacity | 1.2 times rated current allowed,continuous work; 20 times the rated current allowed 1 second | |||
Power Consumption | <0.75VA/phase(Rated current 5A);<0.25VA/phase(Rated current 1A) | |||
Frequency Range | 45~65Hz | |||
Input/Output | Switch Value Input | 2-way passive main line contact DI input, internal supply DC24V power source | ||
Relay Output | 2-way DO output, Contact capacity 250VAC/5A,30VDC/5A | |||
Power Quality Monitor | Harmonic Measurement | Voltage/current2~21th harmonic distortion rate, total harmonic distortion rate. | ||
Harmonic Distortion Rate | Phase voltage,line voltage | |||
Imbalance Rate | Voltage. current | |||
Measurement Accuracy | Voltage | ±0.2%(0.01V) | ||
Current | ±0.2%(0.01A) | |||
Active Power | ±0.5%(0.1W) | |||
Reactive Power | ±2.0%(0.1kvar) | |||
Active Energy | ±0.5%(0.1kWh) | |||
Reactive Energy | ±2.0%(0.1kvarh) | |||
Power Factor | ±0.5%(0.001) | |||
Frequency | ±0.02Hz(0.01Hz) | |||
Temperature | ±1℃(1℃) | |||
Communication | Communication Interface | RS485,Photoelectric isolation interface | ||
Communication Protocol | Modbus-RTU,1200~38400bps | |||
Electrical Insulation | Power Frequency Withstand Voltage | AC2kV/min~1mA Input-output-power source (GB/T 13729) | ||
Insulation Resistance | >50MΩ (GB/T 13729) | |||
Impact Voltage | 5kV(Peak)1.2/50us (GB/T 13729) | |||
Working Environment | Operating Temperature | -25℃ ~ +70℃ | ||
Relative Humidity | 5%~95% No condensation | |||
Storage Temperature | -30℃ ~ +75℃ | |||
Altitude | No more than 4000m |