RPT-III Secondary Current Injection Testing Kits,Relay Protection Analysis Instruments,3 Phase relay protection tester

RPT-III Secondary Current Injection Testing Kits,Relay Protection Analysis Instruments,3 Phase relay protection tester

Negotiable

Min.Order:1

Supply Ability:
1000 per Month
Payment Terms:
T/T Credit Card

Chongqing Top Oil Purifier Co., Ltd

Business Type: Association
Main Products: , , ,

Product Details

RPT-III Secondary Current Injection Testing Kits,Relay Protection Analysis Instruments,3 Phase relay protection tester

 

Product Application

 

RPT-III Relaying protection tester is applied to test  protection replay  based on   voltage and  current operation. The main function of the tester include calibration of voltage and current  operation relays, secondary circuit inspection, trip value of circuit breaker test, switch on and  off time measurement of circuit breaker and so on. It’s a low cost, simple operation and reliable performance device for secondary circuit test.

 

Technical Parameter

1.DC voltage output: 0—350(V)continuity , maximum capacity output:960VA

2.AC voltage output: 0—350(V)continuity , maximum capacity output: 400VA

3.The voltage and current characteristic test for relay coil 

Maximum voltage output is 240V and maximum current output is 5A.The duration time at maximum current is not more than 3 minutes.

4.DC current output:0-10A  continuity, maximum capacity output:80VA

5.AC current output: 0-10A (at maximum voltage 40V)  0-100A((at maximum voltage 14V)  capacity:1000VA  Continuity Output time≤35S

6. AC voltage circuit short connection simulation: voltage output setting≤120V,range15~80%.

7.DC constant voltage alternating output(can be used as operating power of static relay)

Output Voltage: 24V,48V,110V,220V,output current: 0.4A

8. Tester Overload protection

1)DC/AC voltage output circuit:5A fuse

2)DC constant voltage output circuit:0.5A fuse

3) 6A fuse for tester power supply 

9. DC/AC voltmeter and ammeter adopt 4-1/2 digit to transfer,accuracy:0.5 grade

10. Digital timer: 0.000~9999s error: mantissa ±2 digit

11.Symbol definition for time measurement

close operation for open contact from open state 

close operation for close contact from open state

 open operation for open contact from close state 

open operation for close contact from close state 

D  relay operation value test

12.Others

     1)Power supply: 220V±10%,50Hz

     2)Temprature: -20℃~+40℃

     3)Humidity:≤85%(15~25℃)

 

 

 

 

  

 

 

 

 

Our major testers/ analyzers: 

1.Transformer oil breakdown voltage tester ( BDV test kit) series IIJ-II

2. Acidity tester model ACD-3000I

3. Karl Fischer water content tester model TP-6A / model TP-2100

4. Moisture content tester(TPEE)

5. Fully automatic interfacial tension analyzer model IT-800

6. Gas-chromatography transformer oil gas analyzer model DGA2013-1

7. Consolidation point determinator model PT-2000

8. Kinematic viscosity tester model VST-2000

9. Flash point tester (open cup) model TPO-3000

10. Flash point tester (close cup) model TPC-3000

11. Transformer tester (CT/PT tester) model TPVA-404

12. Transformer turn ratio tester model HYG-II

13. Total base number analyzer(TBN tester) TBN-2030

RPT-III Secondary Current Injection Testing Kits,Relay Protection Analysis Instruments,3 Phase relay protection tester