1.Product display
2.Product introduction
BS series measuring transmitters are a kind of device to convert the measured parameters such as current, voltage, power, frequency and power factor to DC current, DC voltage and isolate the output analog signal or digital signals. The transmitters accord with the national standard GB/T 13850 – 1998.
This series digital display AC voltage meters have high environment adaptability because their working temperature range is -40~70℃ and EMC better than III level. They can be applied in control systems, distribution automation systems, industrial automation systems and intelligent buildings.
3.Technical specification
Input |
Rated value |
Current |
1A, 5A |
|
|
Voltage |
100V,220V,380V |
|
Overload |
Continuous |
1.2In,1.2Un |
|
|
Instantaneous |
10In/5s,2Un/1min |
|
Absorption power (each phase) |
Current |
≤0.2VA |
|
|
Voltage |
≤0.2VA |
|
Frequency |
45~65Hz |
|
Output |
Rated value |
0-5V,0-10V,0-5mA,0-20mA,4-20mA (select one)) |
|
|
Load capacity |
Current output load≤ 510Ω, Voltage output load≥20k |
|
|
Output ripple |
≤ 2 times of basic error |
|
|
Accuracy |
0.5 |
|
Power supply |
Working range |
AC/DC 80~270V ,DC19~50V |
|
|
Power consumption |
≤5VA |
|
Response time |
≤400ms |