Features
•Realize online double conversion
•Microprocessor control ensures high reliability
•Input power factor correction
•Output power factor up to 0.8
•Wide mains input range (110 V - 300 V)
•Efficient conversion mode
•Compatible generator
•Optional exquisite SNMP card can be alone or with USB, RS232 together to monitor perfectly
•Through the display, simple operation control, and comprehensive shows the status of monitoring UPS
Specifications
High Frequency Single Phase Online UPS | |||||||||||
Items | C1K (L) | C2K (L) | C3K (L) | C6K (L) | C10K (L) | ||||||
Phase | Single Phase | ||||||||||
Power Rating | 1000 VA / 800 W | 2000 VA / 1600 W | 3000 VA / 2400 W | 6000 VA / 4800 W | 10000 VA / 8000 W | ||||||
Input | |||||||||||
Input Voltage Range/Window | 55-150 VAC or 110-300 VAC at 50% load 85-140 VAC or 160-280 VAC at 100% load | 110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%) | |||||||||
Frequency | 40Hz ~ 70 Hz | 46Hz ~ 54 Hz or 56Hz ~ 64 Hz | |||||||||
Power Factor | 100% load≧0.99 | ||||||||||
Output | |||||||||||
Output Voltage | 200/208/220/230/240VAC | 208/220/230/240VAC | |||||||||
Voltage Range (Battery Mode) | ± 1% | ||||||||||
Frequency(Synchronization correction range) | 47~ 53 Hz or 57 ~ 63 Hz | 46Hz ~ 54 Hz or 56Hz ~ 64 Hz | |||||||||
Frequency (Battery Mode) | 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |||||||||
Surge Ratio | 3:1 | ||||||||||
Harmonic Distortion | ≦ 3% THD (Linear Load) ≦6% THD (Nonlinear Load) | ≦ 3% THD (Linear Load) ≦5% THD (Nonlinear Load) | |||||||||
Transfer Time | AC to DC | 0ms | |||||||||
Inversion to Bypass | 4 ms (Standard ) | 0ms | |||||||||
Waveform(Battery Mode) | Pure Sine Wave | ||||||||||
Efficiency | |||||||||||
Bypass Mode | 88% | 88% | 90% | 92% | 93% | ||||||
Battery Mode | 83% | 85% | 88% | 90% | 91% | ||||||
Battery | |||||||||||
Standard model | Battery Model | 12V / 9AH | |||||||||
Quantity | 2 | 4 | 6 | 16 | 20 | 16 | 20 | ||||
The Max Charging Current | 1.0A(Max) | Preset:1.0 A ± 10%, Max.:2.0A ± 10% | |||||||||
Charging Voltage | 27.4VDC ± 1% | 54.7VDC ± 1% | 82.1VDC ± 1% | 218.4 VDC ± 1% | 273 VDC ± 1% | 218.4 VDC ± 1% | 273 VDC ± 1% | ||||
Long Run model | Battery Model | It ups to the User's requirement | |||||||||
Quantity | 2 | 3 | 4 | 6 | 6 | 8 | 16-20(Adjustable)** | ||||
The Max Charging Current | 1A/2A/4A/6A(Adjustable) | 1A/2A/4A/6A(Adjustable,6A(Only sutible for 16pcs batteries) | |||||||||
Charging Voltage | 27.4VDC ± 1% | 41.0VDC ± 1% | 54.7VDC ± 1% | 82.1VDC ± 1% | 82.1VDC ± 1% | 109.4VDC ± 1% | 273VDC ± 1%(When 20pcs batteries) | ||||
Apperance | |||||||||||
LCD or LED Display | Load size, Battery power, Mains Supply Mode, Battery mode,Failure instruction | ||||||||||
Alarm | |||||||||||
Battery Mode | Sound every 4 seconds | ||||||||||
Low Battery | Sound every second | ||||||||||
Over-load | Sound every second | ||||||||||
Fault | Continuous sounding | ||||||||||
Physical Performance | |||||||||||
Standard model | Size,WxDxH(mm) | 145 X282 X 220 | 145 X397 X 220 | 190 X421 X 318 | 190 x369x688 | 190 x442 x 688 | |||||
Net Weight(KG) | 9.8 | 17 | 27.6 | 61 | 74 | 66 | 75 | ||||
Long Run Model | Size,WxDxH(mm) | 145 X282 X 220 | 145 X397 X 220 | 190 x369 x 318 | 190 x442 x 318 | ||||||
Net Weight(KG) | 4.1 | 6.8 | 7.4 | 12 | 16 | 18 | |||||
Operating Environment | |||||||||||
Temperature & Humidity | Relative humidity 20-90 % and temperature 0- 40°C (No condensation ) | Relative humidity 0-95 % and temperature 0- 40°C (No condensation ) | |||||||||
Noise | less 50dBA @1 Meter | Less 55dBA @ 1 Meter | Less 58dB @ 1 Meter | ||||||||
Control Management | |||||||||||
Smart RS-232 / USB | Support Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC | ||||||||||
SNMP(Option) | Power management support SNMP management and network management | ||||||||||
* When 1-3KVA UPS is set to constant voltage constant frequency mode, the output power will be reduced by 80%. When the output voltage of the UPS is set to 208VAC, the output power will be reduced by 80%. | |||||||||||
* When t 6 / 10KVA UPS is set to constant voltage constant frequency mode, the output power will be down by 60%. When the UPS output voltage is set to 208VAC, the output power will be reduced by 90%. | |||||||||||
*200/208/220/230/240VAC only for long run model UPS(200VAC only for 1-3KVA) | |||||||||||
*Product specifications are subject to us. If any changes, there would be no notice. |