KFD2-CRG2-Ex1.D 24 V DC supply
Negotiable /Piece
Min.Order:1 Piece
Amri (Wuhan) System Engineering Co., Ltd
KFD2-CRG2-Ex1.D 24 V DC supply
1-channel isolated barrier
24 V DC supply (Power Rail)
Input 2-wire and 3-wire transmitters and 2-wire current sources
Output 0/4 mA ... 20 mA
2 relay contact outputs
Adjustable energized/de-energized delay
Programmable high/low alarm
Linearization function (max 20 points)
Line fault detection (LFD)
Up to SIL 2 acc. to IEC 61508/IEC 61511
Interface
Programming interface programming socket
Input
Connection side field side
Connection terminals 1, 2, 3
Input I
Input signal 0/4 ... 20 mA
Available voltage ≥ 15 V at 20 mA
Open circuit voltage/short-circuit current 24 V / 33 mA
Input resistance 45 Ω (terminals 2, 3)
Line fault detection breakage I <0.2 mA; short-circuit I > 22 mA
Output
Connection side control side
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 8+, 7-
Output signal 0 ... 20 mA or 4 ... 20 mA
Output I, II signal, relay
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Mechanical life 5 x 107 switching cycles
Output III Signal, analog
Current range 0 ... 20 mA or 4 ... 20 mA
Open loop voltage max. 24 V DC
Load max. 650 Ω
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)