Building Material Noxious Gas Analysis DIN 53436

Building Material Noxious Gas Analysis DIN 53436

USD $1 - $2 /Set

Min.Order:1 Set

Supply Ability:
10 Set / Sets per Month
Port:
chongqing
Payment Terms:
T/T L/C D/P D/A Credit Card PayPal Other
Delivery Detail:
7 days

Quick Details View All >

Brand Name:
gold
Place of Origin:
China
Model Number:
GD53436

chongqing gold co ltd

Business Type: Manufacturer
Main Products: fire tester ,flame testing instrument ,cone calorimeter ,combustion tester

Product Details

Introduction:

Building material mouse tester for noxious gas analysis is designed accordance to DIN53436 AND . it realized smoke of burning material continuous and stable production and gas extraction, flue gas quantitative description of smoke concentration and accurate calculation of the rate of smoke production, thus it could be used for different circumstances of different materials (including different rates and different concentrations of smoke smoke production) and animal exposure evaluation at different times


International standards:

1. GBT20285-2006
2. DIN53436
3. JIS1321

Technical characteristics:


(1) Temperature range: 300-1000 ºC, control accuracy is not greater than ± 1 ºC (duration greater than 2 min), the dynamic is not greater than ± 2.5 ºC.

(2) Ring furnace heating system showing display time - temperature curve and the actual measured temperature control charts.

(3)Temperature recorders and sheathed thermocouple

(4) Furnace tube diameter: Ф47 + 1-1 mm,  length Ф100 + 10-5 mm

(5) quartz tube

(6) Furnace displacement system: motor drive, speed: 10 ± 0.1mm / min

(7) Air flow: 0-20L / min adjustable

(8)Material smoke production rate could be automatic conversion by system during testing.

(9) The angular velocity chart could be display when the rotation chart squirrel cage

(10) The ring furnace running time arbitrarily set

(11) The smoke toxicity test device has a manual/automatic fast forward, and return function for ring furnace

(12) Each room can be switched to exhaust smoke

(13) Flue gas collection and rationing system realize quickly mix the gas


Control System:

(1) Computer control system: test is more intelligent; curve computer data could be storage and print freely;

(2) Temperature control thermocouple: 1mm K-type thermocouples

(3) The annular heating furnace temperature calibration: time, temperature curve and the actual temperature;

(4) The motor control system, automatic control furnace movement; movement speed is adjustable; and alsocan be adjusted manually;

(5) The system automatically calculates the concentration of smoke production, smoke production rate; squirrel cage speed real-time display;

(6)Temperature range: 300-1000 ºC;

(7) Power: 1.5KW; Heating power: 800-1000W.



Contact Supplier

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Measurement & Analysis Instruments > Analyzers > Other Analysis Instruments
Categories