Eco-friendly Heat Pump Package Unit -Air Cooled Modular Combination 315-504kW

Specifications:

Model   EKAC1100BR1 EKAC1320BR1 EKAC1540BR1 EKAC1760BR1
Unit combination Master unit EKAC220BR1M EKAC220BR1M EKAC220BR1M EKAC220BR1M
slave unit 4*EKAC220BR1S 5*EKAC220BR1S 6*EKAC220BR1S 7*EKAC220BR1S
Nominal cooling capacity kW 315 378 441 504
USRT 89.6 107.52 125 143
×104kcal/h 27.1 32.52 38 43
Nominal heating capacity kW 340 408 476 544
USRT 96.7 116.04 135 155
×104kcal/h 29.25 35.1 41 47
Nominal cooling input power kW 95 114 133 152
Nominal heating input power kW 99 118.8 138.6 158.4
Power supply   380-415V/3Ph/50Hz
Refrigerant Type   R410A
Control   Electronic expansion valve
Compressor Type   Fully hermetic scroll compressor
Lubricant   Grease (POE-160SZ)
Qty. Set 10 12 14 16
Fan Type   Axia fan with large blade and low noise
Qty. Set 10 12 14 16
Water side heat
exchanger
Type          
Water flow for
cooling
m3/h 54 64.8 75.6 86.4
Water flow rate
in heating mode

m3/h
58.5 70.2 81.9 93.6
Water pressure drop kPa 43 43 43 43
Recommended diameter for general inlet/outlet water pipe inch ≥4 ≥5 ≥5 ≥6
Power cable specification Section area of live line
mm2
≥120 ≥150 ≥190 ≥245
Qty. of live lines 3
Section area of null line
mm2
≥4
Qty. of null lines 1
Section area of grounding line
mm2
≥60 ≥75 ≥90 ≥105
Qty. of grounding lines 1
Dimensions L x H mm 2012×1840
Width mm 5860 7105 5860 7105
Unit weight Net weight kg 2575 3090 2575 3090
Operating weight kg 2625 3150 2625 3150

Note
■ Test conditions for nominal cooling capacity: outlet water temperature 7°C; water flow: 0.172m3/(h·kw); outdoor ambient temperature 35°C.Note:

■ Test conditions for nominal heating capacity: outlet water temperature 45°C; water flow: 0.172m3/(h·kW); outdoor dry/web bulb temperature 7°C/6°C.

■ Water resistance at the air conditioner side includes water pressure drop of the unit and the attached Y strainer.

■ Main Pipes of combined units need to be customized and installed on site. The diameter of the pipes must meet design requirements. EK does not provide the pipes.

■ Modular units can be formed usin

Contact Supplier

Mr. Rocky sale Manager Chat Now
Telephone
86-769-83660888
Mobile
86-13510311373
Fax
86-769-83622528
Skype
zhoufang@euroklimat.
Address
Euroklimat Industrial Park Zibo,Shandong

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Mechanical Parts & Fabrication Services > Custom Fabrication Services > Machining Services
Categories
Hi~