Diesel Generator Set Data
Set Type:,XG-1800GF
Standby Power: 1800KW/2250KVA
Prime Power: 1636KW/2045KVA
Rated Current: 2945(A)
Rated Frequency: 50(Hz)
Start-up time: 5~6(s)
Power Factor: 0.8(Lag)
Rated Voltage: 400/230(V)
Standard Features
Engine:Cummins QSK60-G4
Radiator 50℃ max
Fans are driven by belt, with safety guard
24V charge alternator
Dry type air filter, fuel filter, oil filter
Alternator: single bearing alternator
IP23, insulation class H/H
Main line circuit breaker
Standard control panel
Absorber
Muffler
User manual
Diesel Engine Data
Manufacturer: Cummins
Model: QSK60-G4
Prime/Standby Power: 1730KW/1915KW
Rated Speed: 1500(r/min)
Cycle: 4 stroke
Cylinder Arrangement: 6 in line
Displacement: 60.2L
Bore and Stroke: 159*190(mm)
Compression Ratio: 14.5:1
Governor Type: Electronic
Start battery voltage: 24V DC
Air Intake System
Air Intake System: Turbo, Water/Air Cooling
Max Intake Restriction: 6.35kPa
Burning Capacity: 2400L/s
Air Flow: 29600L/s
Exhaust System
Exhaust Gas Flow: 5616L/s
Exhaust Temperature: 450℃
Max Back Pressure: 5.1kPa
Fuel System
Fuel System: HPI PT type fuel pump
100%( Prime Power) Load: 191g/kwh
50%( Prime Power) Load: 194g/kwh
Oil System
Total Oil Capacity: 280L
Oil Consumption: ≤0.4g/kwh
Engine Oil Tank Capacity: 250L
Oil Pressure at Rated RPM: 345-483kPa
Cooling System
Cooling Way: Water-cooled
Total Coolant Capacity: 455L
Thermostat: 82-93℃
Max Water Temperature: 104℃
Alternator Data
Manufacturer: STAMFORD/
SIEMENS/
MARATHON/
ENGGA
Excitation Mode: Brushless and self- exciting
Number of phase and Access Act: 3-phase 4-wire
Connecting Type: “Y” type connecting
Alternator Capacity: 2250KVA
Alternator Efficiencies: 95%
Overload:(PRP)110% load can run 1h
Protection Level: IP22-IP23
Insulation Class, Temperature Rise: H/H
Telephone Influence Factor (TIF): <50
THF: <2%
Voltage Regulation, Steady State: ≤±1%
Air Cooling Flow: 2.69m3/s
Altitude: ≤1000m