Diesel Generator Set Data
Set Type: XG-2000GF
Standby Power: 2000KW/2500KVA
Prime Power: 1818KW/2272KVA
Rated Current: 3272(A)
Rated Frequency: 50(Hz)
Start-up time: 5~6(s)
Power Factor: 0.8(Lag)
Rated Voltage: 400/230(V)
Standard Features
Engine: Cummins QSK60-G11
Radiator 50℃ max
Fans are driven by belt, with safety guard
24V charge alternator
Dry type air filter, fuel filter, oil filter
Alternator: single bearing alternator
IP23, insulation class H/H
Main line circuit breaker
Standard control panel
Absorber
Muffler
User manual
Diesel Engine Data
Manufacturer: Cummins
Model: QSK60-G11
Standby Power: 1955KW
Rated Speed: 1500(r/min)
Cycle: 4 stroke
Cylinder Arrangement: 6 in line
Displacement: 60.2L
Bore and Stroke: 159*190(mm)
Compression Ratio: 14.5:1
Governor Type: Electronic
Start battery voltage: 24V DC
Air Intake System
Air Intake System: Turbo, Water/Air Cooling
Max Intake Restriction: 6.35kPa
Burning Capacity: 2050L/s
Air Flow: 29600L/s
Exhaust System
Exhaust Gas Flow: 5020L/s
Exhaust Temperature: 480℃
Max Back Pressure: 5.1kPa
Fuel System
Fuel System: HPI PT type fuel pump
100%( Prime Power) Load: 195g/kwh
50%( Prime Power) Load: 202g/kwh
Oil System
Total Oil Capacity: 280L
Oil Consumption: ≤0.4g/kwh
Engine Oil Tank Capacity: 250L
Oil Pressure at Rated RPM: 345-483kPa
Cooling System
Cooling Way: Water-cooled
Total Coolant Capacity: 455L
Thermostat: 82-93℃
Max Water Temperature: 104℃
Alternator Data
Manufacturer: STAMFORD/
SIEMENS/
MARATHON/
ENGGA
Excitation Mode: Brushless and self- exciting
Number of phase and Access Act: 3-phase 4-wire
Connecting Type: “Y” type connecting
Alternator Capacity: 2500KVA
Alternator Efficiencies: 95%
Overload:(PRP)110% load can run 1h
Protection Level: IP22-IP23
Insulation Class, Temperature Rise: H/H
Telephone Influence Factor (TIF): <50
THF: <2%
Voltage Regulation, Steady State: ≤±1%
Air Cooling Flow: 2.69m3/s
Altitude: ≤1000m
Genset Electrical Performance
Voltage Regulation: ≥±5%
Voltage Regulation, Stead State: ≤±1%
Sudden Voltage Warp (100% Sudden Reduce): ≤+25%
Sudden Voltage Warp (Sudden Increase): ≤-20%
Voltage Stable Time (100% Sudden Reduce): ≤6S
Voltage Stable Time (Sudden Increase): ≤6S
Frequency Regulation, Stead State: ≤5%
Frequency Waving: ≤1.5%
Sudden Frequency Warp (100% SuddenReduce): ≤+12%
Sudden Frequency Warp (Sudden Increase): ≤-10%
FrequencyRecoveryTime(100%SuddenReduce): ≤5S
FrequencyRecoveryTime(Sudden Increase): ≤5S
Standard Control Panel
Starlight Standard Control Panel uses micro processing technique integrating digital, intelligent and network techniques which can carry out functions including auto start/stop, data measure, alarming. The controller uses LCD display, optional Chinese and English display interface with operation easy and reliable. It can be widely used in all types of generator automatic control system for compact structure, advanced circuits, simple connections and high reliability
Auto Module Control Panel
Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu. Features: 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation. 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect ATS and control directly.
Auto Parallel Control Panel
This new automatic parallel system adopts intelligent modules, inserted and folded installed, no need the peripheral relay and logic circuit. The main switch adopts electronic breaker or frame breaker, combined together with the generator, which is very reliable. One generator, one panel. The panel can be used both for singly and parallel. It is only need to parallel generator with such panel when the capability needs to be enlarged in the future.