NDIR CO2 Controller

Place of Origin Beijing, China
Brand Name Tongdy
Model Number F2000IAQ-CO2-30XX/50XX
Usage Gas Sensor
Theory Other, control for co2
Output Other, on/off, analog output, RS485

Product Features

Specifications

co2 controller: co2 level,temperature,humidity
NDIR infrared CO2 module
application widerly

NDIR CO2 Controller

NDIR CO2 Controller
 

 CO2 Controller Description:

 

CO2 Controller   Application:

 

 F2000IAQ-CO2 monitor/controller is used tomonitoring and control room CO2 level, as well as room temperatureand humidity, provide one or two or three 0~10VDC analog outputs and up tothree dry contact outputs . F2000IAQ-CO2 can be as a programmablelogical controller to control CO2 level, temperature or humidity,and also as a transmitter DDC/PLC controller or other automation systems. Itprovides a RS485 communication interface with an independent address to PC orother control systems.

 

Hotel, exhibition hall, hospital, shop, restaurant, airport, train station, theater and other public places

 

House, villa, office, meeting room, classroom and otherplaces

 

Greenhouse, mushroom, grown room and other agricultural applications

 

 All ventilation systems


CO2 Controller Features:


Multiple functions and high performance with low prices

Wall mounting type and duct type selectable

LCD display detecting both CO2 level andtemperature, also relative humidity (optional)

  NDIR infrared CO2 module inside with special ABC LogicSelf Calibration System. It makes the CO2 measurement more accurate and morereliable in use.

15 years lifetime of CO2 sensor

Microprocessor control, quick response, high precision

  Provide up to three 0~10VDC outputs or relay dry contactoutputs, or up to three mix outputs.

The analog output with two alternatives: linearized overfull range output or PID control output

Different control mode for delays can be selected by user’sapplication, for example for ventilation or for greenhouse or otherapplications.

Locale adjustable range of CO2: 0~20,000ppm or0~50,000;

adjustable range of temperature:5~45°C;adjustable range ofhumidity:5~95%RH

RS-485 communication interface optional, 15KV antistaticprotection, independent base address setting

  CE-Approval

 

NDIR CO2 Controller


You May Like

Find Similar Products By Category

You May Like

View More