Sewage station monitoring module 8DIN+8DO(Relay) Module DAM130 support MODBUS protocol connect to SCADA
USD $40 - $70 /Piece
Min.Order:8 Pieces
Shenzhen King Pigeon Communication Co., Ltd.
DAM Series DAM130
8DIN+8DO(Relay) Module Module
1. Brief instruction
Tips:
King Pigeon Hi-Tech.Co.,Ltd not only provides competitive prices, excellent quality but also helps customers to solve technical problems, improve quality, reduce extra costs, and assist customers to become more competitive. If our existing modules cannot meet your requirements, we also design and manufacture new models / products according to buyer's request. Any of your requirements is always welcome!
2.Mainly Features:
3. Specifications
Items | Specifications |
Rated Power Input
| 10~30VDC(Peak Voltage must≤40V) |
Power Consumption | Typically ≤3W |
Communication Protocol | ModBus RTU |
ModBus Address | 1~247 |
Data Format
| n,8,1; e,8,1; o,8,1 or n,8,2 |
Communication Interface | RS485 |
Baud Rate | 1200, 2400, 4800, 9600, 19200, 38400Bps |
Digital Input | 8 digital input, Dry contact or Wet contact |
Relay Output | 8 relay output(Rated 250VAC@3A or 30VDC@3A ) |
Isolated Type | Digital Input / power / RS485 Serial port use the same GND, Relay Output separately isolated. |
Withstand Tests | Input /Output /Shell: 2000VAC/min.; 500VDC>100 MΩ |
Installation Type | 35mm DIN Rail |
Operation Temperature | -20~70℃; |
Storage Temperature | -40~85℃; |
Relative Humidity | 5~95%RH.;(at -40℃, non condensate) |
Altitude | 0~3000m |
Temperature Drift | ≤100ppm/℃ |
Dimension | 118×72×59mm mm(HxWxD) |
Net Weight | 160g. |