Modbus protocol DAQ BTS monitor modules with 4 digital inputs 8 analog inputs 4 Relay outputs
USD $1 - $10 /Piece
Min.Order:5 Pieces
Shenzhen King Pigeon Communication Co., Ltd.
Distributed Data Acquisition Modules 2-Channel Frequency Measurement Module model
Distributed Data Acquisition Modules 8-Channel Pt Resistance Thermometer Module model
Distributed Data Acquisition Modules 1-Channel Analog Output Module model
Distributed Data Acquisition Modules 8AIN 4 Pt Resistance Thermometer model
data acquisition module rs485 modbus gsm energy meter remote transmitter king pigeon DAM124 series
GSM/GPRS outdoor power failure gsm sms alarm with 2 Relay control (250VAC/10A)
Modbus DAQ BTS monitor modules
Model:DAM124
The DAM124 is for monitoring 4 digital inputs(can be used as pulse counter), 8 analog inputs, controlling 4 triode drivable digital output(50V/100mA, can be TTL or Pulse output). It supports Modbus RTU Protocol over RS485 serial port. Powered up by 10~30VDC.
The DAM124 is used widely in industrial automation control systems. E.g.: Base Transceiver Station, diesel generator rooms, engine room, transformer substations, telecommunication equipment rooms, power supply systems and so on.
The DAM124 is an industrial class, high reliability, low-power consumption, high stability and high precision data acquisition module.
The DAM124 with fire retardant shell, standard 35mm DIN rail makes it easy to install in fields.
2. Mainly Features
3. Specifications
Items | Specifications |
Rated Power Input | 10~30VDC(Peak Voltage must≤40V) |
Power Consumption | Typically ≤3W |
Communication Protocol | Modbus RTU |
Modbus Address | 1~247 |
Data Format | n,8,1; e,8,1; o,8,1 or n,8,2 |
Communication Interface | RS485 |
Baud Rate | 1200, 2400, 4800, 9600, 19200, 38400Bps |
Digital Input | 8 digital input, Dry contact or Wet contact |
Drivable Output | 4 drivable digital output(triode, not relay inside,50V/100mA) |
Analog Input | Default: 4~20mA, optional: 0~20mA, 0~5V, 0~10V |
Update Period | 0.25~2S |
Measurement Precision | ±0.1%FS |
Input Resistance | Analog channel: Voltage:>1KΩ, current ≤150Ω |
Overload Capacity | 1.2 times can sustained,3 times voltage can last 1 second. |
Isolated Type | Digital Input / power / RS485 Serial port / drivable output use the same GND, no isolated. |
Withstand Tests | Input /Output /Shell: 2000VAC/min.; 500VDC>100 MΩ |
Installation Type | 35mm DIN Rail |
Operation Temperature | -20~70℃; |
Storage Temperature | -40~85℃; |
Relative Humidity | 5~95%RH.;(at -40℃, non condensate) |
Altitude | 0~3000m |
Temperature Drift | ≤100ppm/℃ |
Dimension | 118×72×59mm mm(HxWxD) |
Net Weight | 160g. |