Process Technology Temperature Controller AI-516D
USD $50 - $60 /Unit
Min.Order:5 Units
Xiamen Yudian Automation Technology Co., Ltd.
Main Features for Process Technology Temperature Controller AI-516D
Technical Specifications for Process Technology Temperature Controller AI-516D
1. Input type:
Thermocouple: K, S, R, T, E, J, N, B, WRe3-WRe25, WRe5-WRe26.
Resistance temperature detector: Cu50, Pt100.
Linear voltage: 0~5V, 1~5V, 0~1V, 0~100mV, 0~20mV, 0~500mV etc.
Linear current (external precise shunt resist needed): 1~10mA, 0~20mA, 4~20mA etc.
Extended input (install I4 module in MIO): 0~20mA, 4~20mA or two line transmitter.
Optional: apart from the above-mentioned Input type, an additional type can be provided upon request. (Graduation index is needed)
2. Instrument Input range:
K(-50~1300℃), E(0~800℃), S(-50~1700℃), R(-50~1700℃), J(0~1000℃), N(0~1300℃), T(-200~350℃), B(200~1800℃);
Cu50(-50~150℃), Pt100(-200~600℃);
Linear Input: -9990~30000 defined by user.
3. Measurement accuracy:
0.3%FS±1℃ measurement unit.
4. Temperature display resolution:
0.1℃ for K, E, T, N, J, Cu50. Pt100; 1℃ for S, R.
5. Control mode:
On-off control mode (dead band adjustable);
Standard PID with auto tuning;
AI PID with auto tuning, adopting artificial intelligence algorithm.
6. Alarm function:
High limit, Low limit, deviation high limit and deviation low limit; providing the function of alarm blocking at the beginning of power on.
7. Temperature shift:
≤0.015%FS/℃ (typical value is 80ppm.℃)
8. Samplingperiod:
read A/D converter 8 times per second.
9. Power supply voltage rating:
100-240VAC, -15%, +10% / 50-60Hz.
10. Response time:
≤0.5s (when digital filter parameter FILt=0)
11. Control period:
0.24~300.0 seconds selectable, and it should be interger times of 0.5 second.
12. Power consumption:
≤5W.
13. Operation ambient:
Temperature: -10~+60°C, Humidity: 0~90%RH.
Ordering Code Definition for Process Technology Temperature Controller AI-516D
Advanced modularized hardware is utilized for AI series instruments. There are maximum five module slots: multi-function input/ output (MIO), main output (OUTP), alarm (ALM), auxiliary output (AUX) and communication (COMM). The modules can be purchased together or individual, and can be assembled freely. The input type cna be set to thermocouple, RTD, or linear current/ voltage.
The ordering code of AI-516/ AI-516P (V8.2) series instrument is made up of 9 parts. For example:
AI-516 A N X3 L5 N S4 - 24VDC - (F2)
1 2 3 4 5 6 7 8 9
Part 1 Model of the instrument
AI-516/ AI-516P temperature controller
Part 2 Dimension
Size | Front Panel (W*H) | Cut Out (W*H) | Depth Behind Mounting Surface |
A | 96*96mm | 92*92mm | 100mm |
B | 160*80mm | 152*76mm | 100mm |
C | 80*160mm | 152*76mm | 100mm |
D | 72*72mm | 68*68mm | 95mm |
D2 | 48*48mm | 45*45mm | 95mm |
D6 | 48*48mm | 45*45mm | 95mm |
E | 48*96mm | 45*92mm | 100mm |
F | 96*48mm | 92*45mm | 100mm |
E5 | 48*96mm | Rail mounted | 110mm |
Part 3 Multiple Functions I/O (MIO)
I2, I4, K3, V, N, etc.
Part 4 Main Output (OUTP)
L1, L2, L4, W1, W2, G, K1, K5, K6, X3, X5 etc.
Part 5 Alarm (ALM)
Lo, L2, L4, L5, W1, W2, G, etc.
Part 6 Auxiliary Output (AUX)
L0, L2, L4, L5, W1, W2, G, K1, X3, X5, etc.
Part 7 Communication (COMM)
S, S4, V, etc.
Part 8 Power Supply
If let blank, the power of the instrument is 100~240VAC. Added "24VDC" means the power supply is 20~32V DC or AC power.
Part 9 Optional Extended Graduation Specfications
AI-516 series instruments support many input types including popular thermocouples, RTDs, linear voltage, current and resistance inputs. If needed, an additional specification not mentioned in input type selection (InP) table can be extended.
Front Panel and Operation for Process Technology Temperature Controller AI-516D
You will get: