AI-501A Measuring Instruments for Temperature with CE, ISO, UL Certificate
USD $10 - $100 /Unit
Min.Order:5 Units
Xiamen Yudian Automation Technology Co., Ltd.
Main Features for AI-501A Measuring Instruments for Temperature with CE, ISO, UL Certificate
Technical Specifications for AI-501A Temperature Measuring Instruments with CE, ISO, UL Certificate
1. Input type:
Thermocouple: K, S, R, E, J, N.
Resistance temperature detector: Cu50, Pt100.
Linear voltage: 0~5V, 0~1V, 0~500mV,0~100mV, 0~60mV, 0~20mV, 100~500mV, 0~10V, 0~20V.
Linear current (should connect a external resistor or install I4 module in MIO slot): 0~20mA, 4~20mA.
Linear resistor: 0~80ohm, 0~400ohm.
Alternating current: 0~5A.
Alternating voltage: 0~500VAC.
2. Instrument Input range:
K(0~1300℃), S(0~1700℃), R(-0~1700℃), E(0~800℃), J(0~1000℃), N(0~1300℃);
Cu50(-50~150℃), Pt100(-200~800℃);
Linear Input: -9990~30000 unit defined by user.
3. Measurement accuracy:
0.3%FS±1℃ measurement unit.
4. Temperature display resolution:
0.1℃ for K, E, N, J, Cu50. Pt100; 1℃ for S, R.
5. Electromagnetic compatibility (EMC):
IEC61000-4-4, ±4KV/5KHz; IEC61000-4-5, 4KV.
6. Alarm function:
High limit, Low limit, second high limit and second limit.
7. Temperature shift:
≤0.015%FS/℃ (typical value is 75ppm.℃)
8. Retransmission:
When X3 or X5 current module is installed in OUTP slot, process value (PV) can be retransmitted to standard current with maximum load resistor 500ohm.
9. Power supply voltage rating:
100-240VAC, -15%, +10% / 50-60Hz; 24VDC/AC, -15%, +10%.
10. Isolation withstanding voltage:
Between power, relay contact or signal terminals ≥2300VDC; between isolated electroweak signal terminals ≥600VDC.
11. Control period:
0.24~300.0 seconds selectable, and it should be interger times of 0.5 second.
12. Power consumption:
≤5W.
13. Operation ambient:
Temperature: -10~+60°C, Humidity: 0~90%RH.
Ordering Code Definition for AI-501A Measuring Instruments for Temperature with CE, ISO, UL Certificate
The ordering code of AI-501 series instrument is made up of 8 parts. For example:
AI-501 A N X3 L5 N S4 - 24VDC
1 2 3 4 5 6 7 8
Part 1 Model of the instrument
AI-501 Indicating/ Alarming Instrument with dual display measurement accuracy of 0.3%FS.
Part 2 Dimension
Size | Front Panel (W*H) | Cut Out (W*H) | Depth Behind Mounting Surface | Light Bar |
A/A1 | 96*96mm | 92*92mm | A:100mm/ A1:70mm |
|
A2/A21 | 96*96mm | 92*92mm | A2:100mm/ A21:70mm | 25 segments and 4 levels |
B/B1 | 160*80mm | 152*76mm | B:100mm/ B1:70mm | |
B2/B21 | 160*80mm | 152*76mm | B2:100mm/ B21:70mm | 25 segments and 4 levels |
C/C1 | 80*160mm | 76*152mm | C:100mm/ C1:70mm | |
C3/C31 | 80*160mm | 76*152mm | C3:100mm/ C31:70mm | 50 segments and 2 levels |
D | 72*72mm | 68*68mm | 95mm | |
D2 | 48*48mm | 45*45mm | 95mm | |
E/E1 | 48*96mm | 45*92mm | E:100mm/ E1:70mm | |
E2/E21 | 48*96mm | 45*92mm | E2:100/ E21:70mm | 25 segments and 4 levels |
F/F1 | 96*48mm | 92*45mm | F:100/ F1:70mm | |
F0/F10 | 96*48mm (large front) | 92*45mm | F0:100mm/ F10:70mm |
Part 3 Multiple Functions I/O (MIO)
V5/V10, V12/V24, I4, I7, I8
Part 4 Main Output (OUTP)
Installing X3 or X5 (isolated type) current output module can retransmit process value (PV).
Part 5 Alarm (ALM)
Installing L1, L2 or L4 relay output module or L5 dual relay output module to output alarms.
Part 6 Auxiliary Output (AUX)
Installing L1, L2, L4 or L5 relay output module to output alarms.
Part 7 Communication (COMM)
Installing S or S4 module to communicate via RS485 interface.
Part 8 Power Supply
Null indicates 100~240VAC power supply, and "24VDC" indicates 20~32VDC/AC power.
Front Panel and Operation for AI-501A Measuring Instruments for Temperature
Wiring Graph for AI-501A Measuring Instruments for Temperature with CE, ISO, UL Certificate
The compensation wires for different kinds of thermocouple are different, and should be directly connect to the terminals. Connecting the common wire between the compensation wire and the terminals will cause measurement error.
You will get:
A piece of temperature indicator;
A paper of user manual;
One-year/ 3-year warranty card and Quality Approval card;
A lable of units;
A pair of installaton brackets;
Nice package carton box with Yudian logo.