TZH-Y/G-F-06/DD Air Cooling and Desiccant Rotor Coupling Industrial Dehumidifier
Negotiable /Set
Min.Order:1 Set
Dafeng City Sanxing Machinery Manufacturing Co., Ltd.
TZH-Y/G-F-06/DR Heat Pump Regeneration Heating Energy Saving Dehumidifier
TZH-Y/G-F-12/DD Air Cooling Desiccant Rotor Coupling Dehumidifier for Blasting & Coating
TZH-Y/G-F-12/DR Heat Pump Regeneration Heating Energy Saving Dehumidifier
Industrial Air Cooling Machine /Air Cooler Used in Shipyard, Tank Working
1 Products Instruction
TZH-F series movable dehumidifier adopts air cooling freezing and honeycomb desiccant rotors coupling and it is applied for special coating in whole weather. In summer, to use freezing mainly to use desiccant rotor supplement; in spring and autumn, it uses both to do dehumidifying; in winter, it uses desiccant rotor to do dehumidifying.
The refrigerating compressor adopts BITZER screw conveyor for TZH-F series movable dehumidifier. It has functions of 4 stages energy adjustment which is used to improve operation stability of equipments. The cooler adopts air cooled aluminum finned copper tube. The fresh air will go through cooler and dehumidified first and then according to requirements the air will go through desiccant rotor to do dehumidifying further and heating.
According to air inlet condition and air exhaust requirements, PLC will choose different operation status: 100% refrigerating, refrigerating and desiccant rotor, 100% desiccant rotor, refrigerating/desiccant rotor/heating. The above four operation status will meet the different working requirements.
2 Product Characters
2.1 Wide application
Working environmental temperature: -10~40°C
Any environment without erosion.
2.2 Economical operation
Choose operation status automatically according to different air inlet conditions and air exhaust requirements.
Screw compressor 4 stages energy adjusting.
Electrical heating adjustable.
2.3 High accuracy of temperature and humidity of exhausted air
Temperature control accuracy: ±3°C
Humidity control ≤ 45%
2.4 Operation safe and reliable
Protection system for refrigerating unit: high voltage, low voltage, exhausting temperature, phase sequence, default phase, oil shortage, overload.
Protection system for air fan: overload, electric leakage
Protection of electrical heating unit: heating, electric leakage, low air flow
Good water-proof: IP54 protection
2.5 High intelligence, easy operation
Auto control: Sensor + PLC + Touch Screen
Auto control cooling temperature: adjust cooling air fan
Auto control temperature of exhausted air: adjust the output of refrigerating unit and electrical heating.
Auto control regenerating air temperature from desiccant rotor: adjust the electrical heating
Information show: the touch screen will show the operation status, exhausted air temperature, failures etc.
3 Technical Parameters
Model | TZH-Y/G- F-06/DD | TZH-Y/G- F-08/DD | TZH-Y/G- F-12/DD | TZH-Y/G- F-18/DD |
Air Dehumidifying Flow (m3/h) | 6000 | 8000 | 12000 | 18000 |
Compressor Power (kw) | 39 | 48 | 55 | 102 |
Main Air Fan Power (kw) | 7.5 | 11 | 15 | 22 |
After-Heating Power (kw) | 45 | 60 | 90 | 130 |
Regeneration Heating Power (kw) | 36 | 54 | 72 | 105 |
Cooling Power (kw) | 134 | 169 | 197 | 370 |
Total Power (kw) | 134 | 187 | 259 | 383 |
Outer Size of Equipment (mm) | 2000×1900 ×2450 | 3600×2050 ×2600 | 4200×2100 ×2600 | 4300×2300 ×3150 |
Weight (T) | 3.6 | 4.2 | 4.9 | 7.9 |
Temperature control type | High sensitive temperature sensor +PLC auto control +Touch Screen | |||
Air Inlet Condition | Winter: Temperature≥-10°C, RH≤95% Spring & Autumn: Temperature15~20°C, RH≤95% Summer: Temperature≤40°C,RH≤95% | |||
Air Exhaust Condition | Winter: Temperature≥25±3°C, RH≤45% Spring & Autumn: Temperature≤25±3°C, RH≤45% Summer: Temperature≤25±3°C,RH≤45% | |||
Air Exhaust Pressure | ≥1800Pa | |||
Master Control Program | 100%Refrigerating/100% Rotor/Refrigerating+Rotor/100% Heating | |||
Electrical Power | 3 Phase, 380V±10%,50Hz (available to customer's requirements) |