BT200 Used in combination with equipment using brain communication for setting, changing, displaying and printing out parameters
YOKOGAWA BT200 BRAIN TERMINAL
Yokogawa 4 to 20 mA DC signals BT200 BRAIN TERMINAL
As a portable terminal, the Model BT200 BRAIN TERMINAL is used in combination with equipment using brain communication for setting, changing, displaying and printing out parameters such as tag number, output mode, and range, through simultaneous communication. It also monitors I/O values and self-check results, sets constantcurrent output , and allows zero adjustments. The Model BT200 BRAIN TERMINAL is used by connecting it between 4 to 20 mA DC signal transmission lines of the equipment or to a dedicated connector on the ESC (Signal Conditioner Communication Card) when the system is started up or maintained.
FEATURES
Online monitoring and communication
The modulated communication signal does not interrupt the 4 to 20 mA DC signals during communication
Common to all Yokogawa’s equipment
The Model BT200 BRAIN TERMINAL works with all equipment that uses BRAIN communication.
Easy of use
A large display (21 characters by 8 lines) eases setup and alteration procedures in English prompting interactive
sequences.
Diagnostics/security with error messages
Self-check function
Security code protection of setpoints
Low battery voltage alarm
Automatic power-off
Printer (BT200-P00)
Printer prints out tag numbers and other parameters on the spot.
Intrinsic safety (Only for a without printer type)
CSA intrinsically safe approval.