ZW8-12(G) Series Outdoor High Voltage Vacuum Circuit Breaker
USD $800 - $2,000 /Unit
Min.Order:1 Unit
Zhejiang Ghorit 12kv Outdoor High Voltage Vacuum Circuit Breaker ZW10-12
ISO9001 Approved ZW7-40.5 Outdoor High Voltage Vacuum Circuit Breaker
7200v Vacuum Contactor highland type vacuum switch 12kV vacuum contacto
Electrical equipment magnetic contactor 1600A 1.14kV Vacuum Contactor AC contactor
High Voltage Vacuum Contactor 250A 1140V contactor AC vacuum switch
New single pole contactor 1600A vacuum contactor 2KV Vacuum Contactor
ZW8-12 (G)-series outdoor high voltage vacuum circuit breaker is rated voltage 12KV, three-phase AC 50Hz outdoor high voltage switchgear is mainly used to breaking Closing Rural power network , city network and small power system load current, overload current, short-circuit current . The product of the overall structure is box-type three-phase, three-phase vacuum interrupter placed in metal boxes, using SMC insulation material and inter-phase insulation and ground insulation, reliable performance, high dielectric strength.
ZW8-12 (G) is ZW8-12 a composite by circuit breaker and isolating switch, called the combination of circuit breakers, use for disconnect switches
This series of operating mechanism for the CT23-type spring operatingmechanism energy storage can be divided into two kinds of electric and manual.
Mainly Technical parameters
NO | Item | Units | Value | |||
6.3KA | 12.5KA | 20KA | ||||
1 | Rated voltage | KV | 6.3 | 12 | 20 | |
2 | Rated current | A | 16 | 630(1250 ) | 50 | |
3 | Rated short-circuit breaking current | KA | 16 | 12.5 | 50 | |
4 | Rated short circuit closed current(peak) | KA | 6.3 | 31.5 | 20 | |
5 | Rated peak withstand current | KA | 31.5 | |||
6 | Rated short-circuit withstand current | KA | 12.5 | |||
7 | Rated insulation level | power fequency withstand voltage(dry) | 42 | |||
lighting impulse withstand voltage(peak) | 75 | |||||
8 | Rated operating sequence | O-0.3s-CO-180s-CO | ||||
9 | Mechanical life | times | 1000 | |||
10 | Rared short-circuit breaking current breaking times | times | 20 | |||
11 | Rated closing voltage of operation mechanism | V | 110,220 | |||
12 | Rated opening voltage of operation mechanism | V | 110,220 | |||
13 | Contact distance | mm | 11±1 | |||
14 | Over stroke (cmpression length of contact spring) | mm | 3 +1 -0.3 | |||
15 | Three phase closing and opening non-synchronism | ms | ≤ 2 | |||
16 | Contact closing bounce duration | ms | ≤ 2 | |||
17 | Average opening speed | m/s | 1.0±0.2 | |||
18 | Average closing speed | m/s | 0.7±0.15 | |||
19 | Opening time | m/s | 15-50 | |||
20 | Closing time | m/s | 25-50 | |||
21 | Resistance o main loop for each phase | µ Ω | ≤ 0.06 | |||
22 | Permitted accumulate wear-thickness of dynamic and static contact | mm | ≤ 200 |