JCZ5-7.2kV vacuum contactor 160A 250A 400A 630A contactor 12KV Vacuum Contactor
USD $1,100 - $2,500 /Set
Min.Order:1 Set
VC5-12-160/250/400/630
Introduction
VC5-7.2,12/400,630 series vacuum contactor is used in an AC. 50-60 Hz electric power system, with rated working voltage is 7.2Kv and 12kV, and rated current of 400A,630A, for direct or romote on-off control and circuit-breaking control of the of the main load. It is especially suitable for the frequently operated electric control applications such as electric motors, transformer, etc. This series adopts integrated framework, before-and-after layout between the main circuit and controlling circuit, adopts electrical latch or machanical latch, and vacuum interrupter with ceramic shell.
Model
EVC | o | - | o | o | o | / | o | o | - | o | o |
1 | 2 |
| 3 | 4 | 5 |
|
| 6 |
| 7 | 8 |
1. High-voltage AC vaccum contactor
2. Designed code
3. Rated voltage(kV)
4. Latching mode:J—machanical latch; D—electrical latch
5. G—high altitude; Y—movable type; None—basic type
6. Rated current(A)
7. Rated short-time withstand current(kA)
8. Vaccum shell materials: T—ceramic
Main technical specifications
Type form |
| EVC5-12 | ||||||||
Raed work voltage | kV | 12 | ||||||||
Rated work current | A | 160 | 250 | 400 | 630 | |||||
Rated frequency | Hz | 50/60 | ||||||||
Rated thermal current | A | 160 | 250 | 400 | 630 | |||||
Rated making capacity | A | 1600 | 2500 | 4000 | 6300 | |||||
Rated breaking capacity | A | 1280 | 2000 | 3200 | 5040 | |||||
Limit breaking capacity | A | 1600 | 2500 | 4000 | 6300 | |||||
Limit breaking capacity | A/S | 1600/4 | 2500/4 | 4000/4 | 6300/4 | |||||
Operating cycle | Long time | Time/hr | 300 | |||||||
Short time | Time/hr | 600 | ||||||||
Method of operation |
| Non-Latched or Latched | ||||||||
Mechanical endurance | Ops. | 1000000 | ||||||||
Electrical endurance | Ops. | 250000(AC-3) | ||||||||
100000(AC-4) | ||||||||||
Operation voltage | V | AC 120,220 | ||||||||
Closing time | ms | ≤200 | ||||||||
Opening time | ms | ≤160 (electric hold type) | ||||||||
≤60 (mechanical hold type) | ||||||||||
Power frequency | Main circuit | kV | 42 | |||||||
Secondary | kV | 2.0 | ||||||||
Auxiliary switch |
| 3a,3b |